K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
F

Delayed Egress Lock Failure

Alaris Health At BelgroveKearny, New Jersey Survey Completed on 12-05-2024

Summary

The facility failed to meet the delayed egress locking requirements as specified in the NFPA 101 Life Safety Code (2012 Edition). During an observation, it was noted that an exit door between rooms 101 and 118 did not sound an audible alarm after 15 seconds of pressure was applied, as required. The signage on the door indicated that the locks would unlock after 15 seconds and an alarm would sound, but this did not occur. This deficiency had the potential to affect staff and 12 residents. During an interview conducted at the time of the observation, a staff member confirmed the finding and stated that the facility was unaware that the delayed egress lock was not functioning properly.

Plan Of Correction

The delayed egress door for exit between rooms 101 and 118 was repaired to initiate an audible alarm after 15 seconds of pressure is applied to the door. All residents have the potential to be affected by this deficient practice. The Maintenance Director checked all delayed egress doors in the building to assure all had audible alarm after 15 seconds of pressure is applied to the door. All doors were found to be in working order. The Maintenance Director will make monthly rounds to ensure all delayed egress door initiates an audible alarm after 15 seconds of pressure is applied to the door. The Maintenance Director will report the results of these audits to the Administrator on a monthly basis. The Maintenance Director will review the findings of the monthly audits at the Quarterly QAPI Meeting for the next 2 quarters.

Penalty

Fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Egress Door Required Multiple Actions to Unlock
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that an emergency egress door required more than one action to unlock due to a turn button lock, affecting 25 residents in one smoke compartment. The Maintenance Director confirmed the door had been in this condition for an extended period.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙