K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
B

Non-compliant Installation of Hand Sanitizer Dispenser

Highland View Rehabilitation & Healthcare CenterBrockway, Pennsylvania Survey Completed on 02-13-2025

Summary

The facility failed to maintain compliance with the NFPA 101 standards for alcohol-based hand rub dispensers. During an observation, it was noted that a hand sanitizer dispenser was installed directly over an electrical outlet in the main floor corridor near the resident lounge/dining room. This installation does not meet the requirement that dispensers should not be installed within 1 inch of an ignition source. The maintenance director confirmed this deficiency during an interview conducted at the time of the observation.

Plan Of Correction

Maintenance Director will be educated that hand sanitizer dispensers cannot be mounted on walls directly over electrical outlets. Maintenance Director will move the hand sanitizer dispenser so it is not directly over an electrical outlet. Maintenance Director will audit the other hand sanitizer dispensers in the facility to assure they are not mounted on walls directly over electrical outlets.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0325 citations
Improper Placement of ABHR Dispenser Above Ignition Source
E
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

An ABHR dispenser was found installed directly above a light switch, an ignition source, in a resident room. The Director of Maintenance confirmed the noncompliant placement, which did not meet NFPA 101 requirements for ABHR dispenser installation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with ABHR Storage Requirements
D
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

The facility did not meet alcohol-based hand rub dispenser requirements in a smoke compartment. An observation revealed that the basement electric control room had over 10 gallons of hand rub stored outside a cabinet and near an ignition source, with about 40 containers of 40 ounces each. The maintenance director confirmed this deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliant Installation of ABHR Dispensers
D
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

The facility failed to comply with NFPA 101 standards for the installation of alcohol-based hand rub (ABHR) dispensers. During a facility tour, it was found that dispensers in the employee lounge and corridor were installed within one inch of ignition sources, such as light switches and receptacles. These findings were acknowledged by the Maintenance Director and reviewed with the facility's administration.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Placement of ABHR Dispenser
B
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

A facility was found to have an alcohol-based hand rub (ABHR) dispenser improperly mounted above an ignition source in a resident room, violating NFPA 101 safety standards. This deficiency was confirmed by the maintenance supervisor during a survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation of ABHR Above Electrical Outlet
E
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

The facility was found to have improperly installed an Alcohol Based Hand Rub Dispenser (ABHR) directly above a light switch and electrical outlet in the basement kitchen, violating NFPA 101 safety standards. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Placement of ABHR Dispenser
E
K0325 K325: Have properly installed hallway dispensers for alcohol-based hand rub.
Short Summary

The facility failed to maintain alcohol-based hand rub dispensers according to safety regulations. An ABHR dispenser was observed mounted directly above an electrical outlet on the first floor, East, near room 124, which violates the requirement that dispensers should not be installed within 1 inch of an ignition source. This was confirmed during an interview with the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙