K0754 K754: Provide properly sized and located linen or trash receptacles.
D

Improper Storage of Soiled Linen in Facility

St Martha Center For Rehabilitation & HealthcareDowningtown, Pennsylvania Survey Completed on 02-05-2025

Summary

The facility failed to comply with NFPA 101 standards regarding the storage of soiled linen and trash containers. Specifically, the deficiency was observed in two of ten smoke compartments within the facility. On February 5, 2025, at 2:25 PM, soiled linen was found on the floor under the sink in the 300 Wing Tub Room. This observation was confirmed through an interview with the Director of Plant Operations, who acknowledged that the soiled linen was stored outside a rated room or container, which is a violation of the requirement that soiled linen or trash collection receptacles exceeding 32 gallons must be located in a protected space when not attended.

Plan Of Correction

This provider submits the following plan of correction in good faith and to comply with Federal Law. This plan is not an admission of wrongdoing, nor does it reflect agreement with the facts and conclusions stated in the statement of deficiencies. It is the practice of the facility to ensure no excess of receptacles are utilized. 1. The trash containers exceeding thirty-two gallons that were being utilized to store items have been removed and are no longer utilized in the facility and have been replaced with proper storage containers. The linen under the sink in three hundred wing tubs has been removed as well. 2. Facility wide inspection of any trash containers and under sink storage was completed on 2/7/2025. 3. Education with facility wide staff regarding improper disposal of soiled linen and containers needing to be under 32 gallons in shower and tub rooms, to be completed by 3/21/2025. 4. Weekly random audits to be completed for 12 months by Maintenance Director or designee for compliance. This information will then be entered on a log and will be presented to the QAPI meeting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0754 citations
Non-compliance with NFPA 101 for Trash Container Storage
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility failed to comply with NFPA 101 standards by storing three 96-gallon shredder containers in a non-rated ground floor lobby. The containers exceeded the 32-gallon limit for unattended storage without a 1-hour fire-rated protection. The Director of Maintenance confirmed the non-compliance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Storage of Soiled-Linen and Trash Containers
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility did not adhere to NFPA 101 standards by storing soiled-linen and trash containers exceeding 32 gallons in the 1st floor corridor outside a resident's room, rather than in a 1-hour fire-rated room. This was confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Soiled Linen and Trash Container Capacity
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility did not adhere to NFPA 101 standards for soiled linen and trash container capacity, as observed on the 3rd floor Central Bath near a resident room. Containers exceeded the 32-gallon limit in a 64-square foot area, confirmed by maintenance staff. A follow-up observation showed the issue remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Soiled Linen and Trash Container Standards
E
K0754 K754: Provide properly sized and located linen or trash receptacles.
Short Summary

The facility failed to comply with NFPA 101 standards by allowing accumulated trash and soiled-linen containers to reach 32 gallons in a 64-square foot area on the 3rd floor Central Bath, near a resident room. This was outside a protected area, violating the requirement for such containers to be within a protected hazardous area if exceeding the specified capacity. The Director of Maintenance confirmed the oversight.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙