K0293 K293: Have properly located and lighted "Exit" signs.
F

Deficiency in Exit Signage Maintenance

Kittanning Health & Rehab CenterKittanning, Pennsylvania Survey Completed on 01-22-2025

Summary

The facility failed to maintain proper exit and directional signage throughout the building, as required by NFPA 101 standards. During a survey conducted on January 22, 2025, it was observed that the MIU unit courtyard doors had blinds covering the 'NOT AN EXIT' signs, obstructing visibility. Additionally, the facility was unable to provide documentation for monthly exit sign inspections for the previous 12 months. These deficiencies were confirmed during an interview with the maintenance supervisor on the same day.

Plan Of Correction

A. MIU Courtyard Door: Maintenance immediately removed all blinds that were covering courtyard "NOT AN EXIT" sign. Maintenance completed exit sign inspection and documented findings. No additional negative findings. NHA/Designee to educate maintenance staff by 21MAR2025 on exit signage visibility. Maintenance/designee will complete weekly x 4 audits of exit signage to ensure proper display. Negative findings will be addressed accordingly. Ad Hoc education as needed. The results of the audits will be forwarded to the facility Quality Assurance Performance Improvement (QAPI) committee for further review and recommendations. B. Facility couldn't provide documentation for monthly 12 month exit sign inspection: Maintenance performed immediate exit sign inspection and documented findings. Maintenance will keep proper documentation for monthly exit sign inspection. NHA/Designee will educate Maintenance staff by 21MAR2025 on exit sign inspection and documentation. NHA/Designee will complete exit sign inspection documentation audits monthly x 3 audits to ensure proper inspection and documentation. Negative findings will be addressed accordingly. Ad Hoc education as needed. The results of the audits will be forwarded to the facility Quality Assurance Performance Improvement (QAPI) committee for further review and recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0293 citations
Failure to Maintain Continuous Illumination of Exit Sign
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that an exit sign above the door leading to grade from the stairtower near the Elevator Lobby was not illuminated as required. This lack of illumination was confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illuminated Exit Signage
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

A deficiency was identified when an exit sign near a resident room in one smoke compartment was found to be unilluminated, as confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Monthly Exit Sign Inspections
C
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that the facility did not have documentation to verify that monthly visual inspections of exit signs were completed over the past year. This was confirmed by the DON and Director of Maintenance during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Signs Not Illuminated on Emergency Power
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit signs in the older section of the facility failed to illuminate when tested for battery back-up, indicating they were not transferring to emergency power as required. The maintenance director believed the signs were working, but testing and observation confirmed the deficiency, which could affect 50 occupants during a power outage.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Sign with Battery Backup Failed to Illuminate During Test
D
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

An exit sign with a battery backup near the kitchen corridor failed to illuminate when tested, as observed during a facility tour and confirmed by the Environmental Supervisor. This deficiency affected 15 residents and one smoke compartment, indicating the exit sign was not maintained in accordance with NFPA 101 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Exit Signage and Egress Configuration
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit and directional signs were not properly displayed or configured, with the emergency exit sign outside the Saginaw Room Dining space set up incorrectly. This left the North side of the facility without an emergency exit from resident spaces, and the exit configuration did not match the emergency placards in the corridors. These issues were confirmed by the maintenance director during the survey.

Fine: $30,740
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer