K0293 K293: Have properly located and lighted "Exit" signs.
B

Exit Signage Deficiencies Noted in Facility

Lecom At Presque Isle, IncErie, Pennsylvania Survey Completed on 01-16-2025

Summary

The facility failed to maintain proper exit signage as required by NFPA 101, Section 7.10, which mandates continuous illumination of exit and directional signs, also served by the emergency lighting system. During an observation conducted on January 16, 2025, between 11:32 a.m. and 12:35 p.m., four deficiencies were noted in the exit signage on the main floor. Specifically, missing directional exit signs were observed in the main floor corridor from Ambassador to the North nurse station, the main floor entrance corridor to the North/South corridors, the main floor employee hall to the main corridor, and the main floor Northwest hall towards the North nurse station. An interview with the maintenance manager confirmed these deficiencies at the time of the survey.

Plan Of Correction

The directional exit signs for the following corridors have been installed: A. Main floor corridor to North Nurse station B. Main floor corridor to the North/South corridors C. Main floor employee hall to the main corridor D. Main floor Northwest hall toward the north Nurse station The maintenance director and/or designee will ensure that the facility directional signs will be maintained with continuous illumination.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0293 citations
Failure to Maintain Continuous Illumination of Exit Sign
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that an exit sign above the door leading to grade from the stairtower near the Elevator Lobby was not illuminated as required. This lack of illumination was confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Illuminated Exit Signage
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

A deficiency was identified when an exit sign near a resident room in one smoke compartment was found to be unilluminated, as confirmed by the Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Monthly Exit Sign Inspections
C
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Surveyors found that the facility did not have documentation to verify that monthly visual inspections of exit signs were completed over the past year. This was confirmed by the DON and Director of Maintenance during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Signs Not Illuminated on Emergency Power
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit signs in the older section of the facility failed to illuminate when tested for battery back-up, indicating they were not transferring to emergency power as required. The maintenance director believed the signs were working, but testing and observation confirmed the deficiency, which could affect 50 occupants during a power outage.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exit Sign with Battery Backup Failed to Illuminate During Test
D
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

An exit sign with a battery backup near the kitchen corridor failed to illuminate when tested, as observed during a facility tour and confirmed by the Environmental Supervisor. This deficiency affected 15 residents and one smoke compartment, indicating the exit sign was not maintained in accordance with NFPA 101 requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Exit Signage and Egress Configuration
E
K0293 K293: Have properly located and lighted "Exit" signs.
Short Summary

Exit and directional signs were not properly displayed or configured, with the emergency exit sign outside the Saginaw Room Dining space set up incorrectly. This left the North side of the facility without an emergency exit from resident spaces, and the exit configuration did not match the emergency placards in the corridors. These issues were confirmed by the maintenance director during the survey.

Fine: $30,740
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙