K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
E

Delayed Egress Door Malfunction

Valley Manor Rehabilitation And Healthcare CenterCoopersburg, Pennsylvania Survey Completed on 03-12-2025

Summary

The facility failed to maintain proper functioning of exit egress doors equipped with delayed egress locking arrangements. During an observation on March 12, 2025, it was noted that two exit doors did not release after 15 seconds of applying pressure against the crash bar, as required. These doors were located on the first floor, specifically door # EM-1 next to the basement stairwell and door # E4 in the dining room. The deficiency was confirmed during an exit interview with the Administrator, Director of Maintenance, and Assistant, who acknowledged that the doors did not release as expected. This issue affected two of the four smoke compartments in the facility, indicating a failure to comply with the necessary safety standards for egress doors.

Plan Of Correction

1. Door # EM1 repaired and released on egress and requesting a TLW for EM4 as a door repair may be necessary to be made by an outside vendor. 2. 4/28/25 3. Doors will be checked on a monthly basis. 4. Director of maintenance or designee will conduct monthly audits to ensure doors are released after 15 seconds of applying pressure.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Egress Door Required Multiple Actions to Unlock
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that an emergency egress door required more than one action to unlock due to a turn button lock, affecting 25 residents in one smoke compartment. The Maintenance Director confirmed the door had been in this condition for an extended period.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙