K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
F

Failure to Perform Annual Electrical Inspections

Valley Manor Rehabilitation And Healthcare CenterCoopersburg, Pennsylvania Survey Completed on 03-12-2025

Summary

The facility failed to maintain the required inspections of electrical wiring and receptacle systems, which affected all resident bed locations. During a documentation review on March 12, 2025, it was revealed that the annual inspection of receptacles in resident care areas was not performed. This deficiency was confirmed during an exit interview with the Administrator, Director of Maintenance, and Assistant on the same day.

Plan Of Correction

Facility will conduct annual receptacle testing in resident care areas. 4/28/25 Maintenance staff educated on receptacle testing. The Director of maintenance will conduct random facility audits.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0921 citations
Failure to Maintain and Inspect Patient-Care Electrical Equipment
E
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that fixed patient-care electrical equipment was not properly maintained or inspected in accordance with NFPA 99. In one room, a bedside remote had mismatched insulation and exposed wiring, and in another room, a call button receptacle had exposed low-voltage conductors. The Maintenance Director acknowledged both issues and reported that new bed remotes had been received but not yet installed.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Annual Testing Documentation for Patient-Care Electrical Equipment
F
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that the facility did not maintain required documentation showing that annual NFPA 99-compliant testing (including physical integrity, resistance, leakage current, and touch current tests) was performed on electrical equipment used for patient care. During record review with the Maintenance Director, no records could be produced to verify that this testing had been completed as required, and the Maintenance Director acknowledged the lack of documentation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Patient-Care Electrical Equipment per NFPA 99
D
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

Surveyors found that patient-care related electrical equipment was not inspected and maintained in accordance with NFPA 99 requirements. Biomedical inspection records showed that inspections were not current, and an observation in the gym revealed two microwaves, a toaster oven, and an "E Stem" device with overdue inspection stickers from 2024. During an interview, an assistant reported that this equipment was supplied by the corporate office and maintained by a different company, yet the items remained in use in a patient-care area without up-to-date inspections, affecting one of seven smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test Electrical Equipment Before Use
E
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

A portable blood pressure machine in the facility was found to be in use without undergoing the required Bio-Medical testing. The machine had been used daily for over two months, as confirmed by a staff nurse and the Director of Maintenance. This deficiency was acknowledged by the facility's administration during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Electric Beds as per Manufacturer's Guidelines
D
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

The facility did not ensure proper maintenance of electric beds as per the manufacturer's guidelines. During a survey, it was found that electrically operated beds were not inspected at the required intervals, and there was no documentation of formal inspections or maintenance. The Environmental Services Director acknowledged the lack of unique identifiers for beds and stated that beds were checked annually using a room audit form, but specific beds were not identified. This failure to adhere to maintenance requirements constituted a deficiency in compliance with NFPA 99 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document and Verify Annual Electrical Receptacle Inspections
K0921 K921: Ensure that testing and maintenance of electrical equipment is performed.
Short Summary

The facility did not provide adequate documentation to verify that all electrical receptacles in patient care areas were inspected and tested annually as required, and the records submitted lacked itemized details and inspection criteria, making it impossible to confirm compliance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙