K0311 K311: Have an enclosure around a vertical opening shaft.
B

Failure to Maintain Fire Resistance Rating for Vertical Openings

Bryn Mawr VillageBryn Mawr, Pennsylvania Survey Completed on 03-17-2025

Summary

The facility failed to maintain the required fire resistance rating for vertical openings, specifically affecting two levels within the building. During a document review and interview conducted on March 17, 2025, it was discovered that the communicating stairway between the Lower Level Kitchen and the First Floor did not have the necessary one-hour fire resistive construction. This deficiency was confirmed during an exit interview with the Administrator and Maintenance Director. Additionally, the facility did not maintain the fire resistance rating for stair towers, impacting one of two floors within the building. A document review revealed that the north side exit from the Basement was a communicating staircase with walls not sheathed on the room 2A side, lacking the required one-hour fire resistance rating. This issue was also confirmed during an exit interview with the Administrator and Maintenance Director.

Plan Of Correction

The facility will work with an outside consultant to complete an FSES to cover this deficiency. The Administrator or designee is responsible for monitoring this and, as part of the Quality Assurance Performance Improvement Program, will report on Life Safety requirements and plan of correction to the Committee. The facility will work with an outside consultant to complete an FSES to cover this deficiency. The Administrator or designee is responsible for monitoring this and, as part of the Quality Assurance Performance Improvement Program, will report on Life Safety requirements and plan of correction to the Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0311 citations
Failure to Maintain Self-Closing Mechanism on Laundry Chute Door
B
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

A basement laundry chute door was found to lack the required number of fusible links on its hold-open springs, preventing the door from closing as mandated. This deficiency was confirmed by both the administrator and maintenance supervisor during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Vertical Opening Enclosures
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain proper vertical opening enclosures, as unsealed openings were found in a bathroom pipe chase wall on two unoccupied floors. This was due to ongoing work to replace a leaking drain pipe, affecting two smoke compartments. The issue was confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Resistance Rating on Tenth Floor
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility did not maintain the fire resistance rating of vertical openings on the tenth floor. An observation revealed that the rated access ceiling door in the Electrical Closet next to room 1020 failed to self-close and latch, as confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Vertical Opening Enclosure Deficiency
D
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility did not maintain the required fire resistance rating for vertical opening enclosures, affecting one smoke compartment. Observations revealed multiple wires passing through a large open hole in Room U 115, confirmed by the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Inadequate Fire Resistance in Vertical Enclosures
C
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain the required fire resistance rating for vertical enclosures, affecting all six floors. Observations revealed that HVAC shafts adjacent to exit stair towers lacked the necessary two-hour fire resistance. Additionally, the Clay Street exit stair tower on the fourth and fifth floors had inadequate construction, with insufficient drywall and unprotected steel beams. This deficiency was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Vertical Opening Fire Safety Deficiency
E
K0311 K311: Have an enclosure around a vertical opening shaft.
Short Summary

The facility failed to maintain fire safety for a vertical opening between two floors. The self-closing devices were removed from the Private Dining Room's double doors, which are part of a one-hour, two-story vertical opening. This deficiency was confirmed during an interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙