K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
E

Deficiencies in Hazardous Area Enclosures

Crown Heights Center For Nursing And RehabBrooklyn, New York Survey Completed on 12-19-2024

Summary

The facility failed to ensure that all hazardous areas were properly enclosed in accordance with the 2012 NFPA 101 standards. During a life safety survey, several deficiencies were observed on the first floor. In the generator room, a plywood wall covering was not labeled as fire-resistant, and there was a large opening in the concrete wall that communicated with the adjacent automatic transfer switch room. Additionally, the door to this room was propped open. The automatic transfer switch room lacked sprinkler coverage, had missing ceiling tiles exposing unprotected steel beams, and wall penetrations were sealed with non-approved fire blocking foam. The trash compactor room door was not self-closing and lacked a latch due to missing hardware. Similarly, the boiler room door was missing hardware, allowing smoke to pass into the corridor. Lastly, the maintenance shop room door was held open with a magnet not connected to the fire alarm system.

Plan Of Correction

Plan of Correction: Approved January 13, 2025 Element 1 K321 Corrective Action: The maintenance director immediately audited all areas within the building to ensure any hazardous area has a 1-hour fire resistance rating, and the areas shall be separated from other spaces by smoke partitions in accordance with 2012 edition of NFPA 101. The following corrections have been made: On 12/20/2024, the concrete wall surrounding the generator room had an opening of 3-4', communicating with the adjacent transfer switch room. This area has been sealed with concrete blocks to comply with a 1-hour fire rating. The tiles missing in the automatic transfer switch room were replaced. On (MONTH) 13, 2025, the door to the trash compactor room had the hardware replaced to include a panic bar door handle and latch to ensure the door was self-closing. On (MONTH) 13, 2025, the hardware on the boiler room door was replaced to ensure it was self-closing and did not allow the penetration of smoke. All penetrations in the walls that were sealed with fire blocking foam have been removed and replaced with an approved fire rated stopping material. Element 2 Residents at Risk: While no other residents were affected by this practice, the potential existed for all residents and staff to be affected by this practice. All hazardous areas were inspected for similar deficiencies. None were found. Element 3 The policy and procedure for hazardous doors was reviewed and revised. All maintenance staff will be in-serviced on 2012 NFPA 101 19.3.2.3 hazardous areas shall be safeguarded with a 1-hour fire rating. Documentation checklist for Life Safety Code Standards Observations will be implemented and include all components of hazardous areas shall be safeguarded by a fire barrier having a one-hour resistance rating. Any negative findings will be addressed immediately. An audit tool was developed to monitor compliance. Element 4 Monitoring of Corrective Action: The maintenance director or designee will inspect all Hazardous Areas to ensure all areas are safeguarded by a fire barrier having a 1-hour fire resistive rating. The findings of all these audits to inspect all Hazardous Areas to ensure a 1-Hour Fire Rating will be reviewed monthly and reported to the Administrator. The maintenance director or designee will report findings to the QAPI Committee quarterly for a period of 6 months. The QAPI Committee will determine any further actions. Element 5 Person Responsible: Maintenance Director

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0321 citations
Failure to Maintain Self-Closing Doors for Multiple Hazardous Storage Areas
F
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that multiple hazardous storage areas, including a closet near medical records, a beauty salon used to store chemical cases, a supply room in one nursing station, a room leading to a smoking area, a housekeeping room near therapy, and a lobby storage room, lacked required self-closing or automatic-closing doors. These conditions did not comply with NFPA 101 requirements for hazardous area enclosure and had the potential to affect all residents and staff in an emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Soiled Linen Room Door Failed to Latch in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the common area soiled linen room on the second floor, classified as a hazardous area in a sprinklered location, had a door that failed to positively latch when tested. This door is required to self-close and latch to maintain proper separation for hazardous areas. The issue was confirmed with the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Fire Barrier Door Closure in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A faulty door closure was observed on the South Nurses' Station and Food Storage Room, resulting in the door failing to automatically close and latch as required for hazardous area enclosures. This deficiency was confirmed by the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Self-Closing and Latching Door in Hazardous Area
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors found that the door to a third-floor trash room, classified as a hazardous area, did not self-close or positively latch as required. This issue was confirmed by facility staff during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Failed to Self-Close and Latch
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

A deficiency was found when the A Hall Resident Care Supply room door did not self-close to a positive latch as required by LSC 8.7.1.3, leaving a hazardous area inadequately protected according to fire safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Hazardous Area Door Deficiencies and Improper Hold-Open Devices
E
K0321 K321: Ensure that special areas are constructed so that walls can resist fire for one hour or have an approved fire extinguishing system.
Short Summary

Surveyors identified that hazardous area doors, including the Sprinkler Tank Room and 1st floor Dietary Storage Room, were not maintained within required gap margins and were held open with unauthorized devices, as confirmed by the Director of Facilities.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer