K0363 K363: Install corridor and hallway doors that block smoke.
E

Corridor Doors Not Smoke-Resistant

Spring Creek Rehabilitation & Nursing Care CenterBrooklyn, New York Survey Completed on 02-12-2025

Summary

The facility failed to ensure that all corridor doors were maintained to resist the passage of smoke, as required by safety regulations. During a life safety survey conducted on February 10, 2025, it was observed that transfer grilles were present on corridor doors across multiple floors, specifically on floors 1 through 4. These grilles were found on the doors to janitor's closets near rooms 4C25 and 4D08 on the 4th floor, near rooms 3A08, 3D08, and 3B25 on the 3rd floor, near rooms C25 and D08 on the 2nd floor, and on the utility room door near the activities room on the 1st floor. The presence of these grilles violates the requirement that corridor doors must be constructed to resist the passage of smoke, as outlined in the 2012 NFPA 101 and 2011 NFPA 25 standards, as well as 10 NYCRR 711.2 (a).

Plan Of Correction

Plan of Correction: Approved February 24, 2025 I. Immediate Corrective Action The transfer grilles which were found on corridor doors in the following locations were closed off with metal plates: 1) On the doors to the janitor's closets near rooms 4C25 and 4 DO8 on the 4th floor. 2) On the 3rd floor janitor's closets near rooms 3A08, 3D08 and 3B25. 3) On the 2nd floor near rooms 2C25 and 2D08. 4) On the 1st floor on the utility room near the activities room. II. Identification of Other Residents a. An audit has been conducted of all corridor doors throughout the facility to make sure all doors close and latch as required with proper sealing to prevent the transfer of smoke. b. No additional doors were found noncompliant. c. No residents' additional residents were found to be affected upon completion of this review. III. Systemic Changes 1. The facility has reviewed the Preventive Maintenance Plan and door inspection policy and revised the same to include directives for ventilation grilles, as well as inspection observations. 2. All Maintenance staff will be educated by the maintenance director on the Preventive Maintenance Plan and requirement for appropriate Door operation. 3. The Lesson Plan will concentrate on the following: > Overview of requirements for K363 > Preventive Maintenance plan for performing observational inspections of the doors > Responsibility for providing appropriate door closures. 4. A copy of the Lesson Plan and attendance will be filed for reference and validation. a. The facility reviewed and revised its policy regarding corridor doors. b. All maintenance staff were in service on the updated corridor door policies. IV. QA monitoring a. An audit tool was created to monitor the facility’s corridor doors. b. Monitoring of the facility’s doors shall be performed monthly for the first 3 months and then quarterly thereafter for 9 months. c. Any negative findings from inspections shall be reported to the administrator for further evaluation and will be addressed. d. All reports shall be brought to the Quality Assurance meeting to review with the team to ensure that repairs are being performed in a timely manner for 12 months. V. Title Responsible Director of maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations
Failure of Corridor Door to Latch Properly
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that a corridor door to a resident room on one floor failed to latch into the frame when tested, meaning it did not meet NFPA 101 requirements for positive latching of corridor doors. The Facilities Manager and Facility Life Safety staff confirmed during interview that this corridor door did not latch properly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Multiple Corridor Door Deficiencies Impacting Smoke and Fire Protection
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors identified several corridor door deficiencies, including doors that failed to latch, lacked smoke tight integrity, and had missing locksets, across multiple floors. These issues were confirmed by facility leadership during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Properly Latching Corridor Doors
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors, one on the third floor and one on the second floor, did not latch when tested, affecting two smoke compartments. The Facility Administrator and Maintenance Director confirmed these deficiencies, which were not in compliance with fire and smoke protection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Positive Latching of Corridor Door
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

A corridor door leading to the Patio Lounge failed to positively latch within the door frame, as observed and confirmed by the Director of Maintenance. This deficiency affected one of twelve smoke compartments and did not meet NFPA 101 and CMS requirements for corridor door latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Corridor Doors for Smoke Resistance and Latching
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that corridor doors to two resident rooms did not close and latch properly, as confirmed by the facility's Administrator and Maintenance Director. This deficiency affected one of five smoke compartments and did not meet regulatory requirements for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Corridor Doors Blocked Open with Wedges
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two resident rooms had wooden door wedges holding corridor doors open, preventing them from closing as required for fire safety. Facility staff confirmed that the wedges impeded proper door closure.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙