K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Deficiencies in Sprinkler System Maintenance

Briarcliff Manor Center For Rehab And Nursing CareBriarcliff Manor, New York Survey Completed on 03-20-2025

Summary

The facility failed to maintain its automatic sprinkler and standpipe systems in accordance with NFPA 101 and NFPA 25 standards. During a life safety recertification survey, it was observed that the quarterly sprinkler report for the third quarter of 2024 was missing. Additionally, several sprinklers in the laundry room, dishwashing room, and family lounge area exhibited signs of corrosion and were missing escutcheon plates. Water pressure gauges on the sprinkler system were outdated, and documentation of their re-calibration or replacement was not provided. An unknown substance was also found on the sprinklers in the Beauty Salon. Interviews with the Director of Maintenance revealed that the facility had not yet addressed these issues, although the Director stated that a vendor would be contacted to assess the sprinklers. These deficiencies were noted in the basement and on one of the two resident floors, indicating a widespread issue with the maintenance of the facility's fire protection systems.

Plan Of Correction

Plan of Correction: Approved April 10, 2025 K353 I. Immediate Corrective Action: 1. Quarterly Sprinkler Report for 2024: - On 3/19/25, the Director of Maintenance contacted the sprinkler service vendor to request the missing third-quarter report for 2024. - The report was obtained on 3/20/25 and placed in the facility’s records to ensure compliance with NFPA 101 and NFPA 25. 2. Sprinkler Corrosion and Missing Escutcheon Plates: - On 3/19/25, the Director of Maintenance immediately contacted a certified sprinkler contractor to assess and address the corrosion and missing escutcheon plates on sprinklers in the laundry room, dishwashing room, family lounge area, and Beauty Salon. - The vendor inspected and replaced corroded sprinklers and installed missing escutcheon plates on 3/20/25. 3. Water Pressure Gauges: - On 3/19/25, the Director of Maintenance arranged for the recalibration or replacement of outdated water pressure gauges. - The water pressure gauges have been replaced by a certified vendor. 4. Substance on Sprinklers (Beauty Salon): - On 3/19/25, the Director of Maintenance immediately arranged for the cleaning and inspection of the sprinklers in the Beauty Salon, where an unknown substance was found. - The sprinklers were replaced on 3/20/25. II. Identification of Others: - The Director of Maintenance conducted a full inspection of all sprinkler systems in the facility, including those in other common areas, to ensure no additional sprinklers were corroded or missing escutcheon plates. - All residents have the potential to be affected. - No additional issues were found, but ongoing checks will be implemented to prevent future occurrences. III. Systemic Changes: 1. The Director of Maintenance reviewed the facility’s sprinkler maintenance policy to ensure all quarterly sprinkler inspections are properly documented and provided in a timely manner. - Maintenance staff will now inspect all sprinklers monthly for six months to ensure no corrosion or damage is present. IV. Quality Assurance: 1. A new audit tool was created by the Director of Maintenance to track the status of sprinkler system maintenance, including quarterly inspections and repairs. 2. The results of monthly audits will be reported to QAPI quarterly, with any corrective actions taken promptly. V. Person Responsible: - Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments