K0351 K351: Install an approved automatic sprinkler system.
F

Incomplete Sprinkler System Installation in Electrical Room

Bryn Mawr Extended Care CenterBryn Mawr, Pennsylvania Survey Completed on 04-15-2025

Summary

The facility failed to install required sprinkler system components, specifically in the Main electrical (switchgear) Room located in the basement. This deficiency was identified during an observation on April 15, 2025, at 11:25 a.m. The absence of an automatic sprinkler system in this area was confirmed during an exit interview with the Administrator, Maintenance Director, and Regional VP of Operations on the same day at 2:45 p.m. This oversight affects one of the three levels of the facility, indicating incomplete automatic sprinkler protection as per the requirements outlined in NFPA 101 and NFPA 13 standards.

Plan Of Correction

1) The facility contractor is submitting plans to the Plan Review Department for approval of modifications to the fire suppression system for approval. 2) The Maintenance Director and/or designee will inspect the Main Electrical Room once a suitable fire suppression system is installed. 3) To prevent the potential for reoccurrence, the Administrator will educate the Maintenance Director and/or designee on the importance of a suitable fire suppression system is installed. 4) To monitor and maintain ongoing compliance, the Administrator and/or designee will check the fire suppression system is in place as required monthly for 3 months. Findings will be reported to facility QAPI for continued review and recommendations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0351 citations
Incomplete Sprinkler Coverage for Built-In Dining Room Cabinetry
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that floor-to-ceiling built-in millwork cabinetry with doors in the first floor dining room was installed and in use without interior sprinkler coverage or other required fire protection measures, and this cabinetry was not shown on the approved DOH renovation and sprinkler plans, preventing verification of proper sprinkler coverage; on revisit, the same lack of fire protection within the closed-door storage cabinetry remained uncorrected, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Sprinkler System Installation
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A deficiency was cited due to the facility not being fully protected by an approved automatic sprinkler system as required by the 2012 standards for existing nursing homes and hospitals.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Obstructions and Missing Ceiling Tiles
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

Surveyors found that shower curtains in multiple resident rooms were within 18 inches of sprinkler heads, violating NFPA 13 requirements, and also noted missing ceiling tiles in two utility areas. These issues were confirmed by the Facilities Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Sprinkler Pipe for Mechanical Support
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A hot water pipe was observed being supported and hanging from a sprinkler pipe in the 300 wing mechanical room, contrary to NFPA 13 requirements for sprinkler system installation. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Sprinkler System Deficiency in Elevator Pit
E
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

The facility failed to maintain sprinkler system requirements as the hydraulic elevator pit lacked a sidewall sprinkler installed within two feet of the floor. This deficiency was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Attic Sprinkler System Not Installed per NFPA 13
F
K0351 K351: Install an approved automatic sprinkler system.
Short Summary

A review of facility records revealed that the dry sprinkler system in the attic had been capped off, leaving the attic without full sprinkler protection as required by NFPA 13. This was confirmed by the Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙