K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
D

Egress Door Compliance Failure

Willowbrooke Court At St Andrews EstatesBoca Raton, Florida Survey Completed on 04-29-2025

Summary

The facility failed to maintain their egress doors equipped with delayed egress locking arrangements in accordance with NFPA 101 standards. During a facility tour conducted on April 29, 2025, between 1:15 PM and 2:45 PM, it was observed that the delayed egress doors located in the Coconut Grove hallway did not open when tested. This issue was identified in the presence of the Director of Property Management, who was accompanying the surveyors during the inspection. An interview with the Administrator and the Director of Property Management was conducted concurrently with the observations, during which they acknowledged the findings. The deficiency was reviewed with both the Administrator and the Director of Property Management at the exit meeting on the same day at 3:00 PM. The failure to maintain the egress doors in compliance with the NFPA 101 standards was documented as a deficiency, specifically noting the non-compliance with the delayed egress locking arrangements.

Plan Of Correction

The statement made on this Plan of Correction are not and do not constitute an agreement with the alleged deficiencies herein. To remain in compliance with all federal and state regulation the center has taken or will take the actions set forth in the following plan of correction. The following plan of correction constitutes the center's allegation of compliance such that all alleged deficiencies cited have been or will be corrected by the date indicated. **K222 Egress Doors** Immediate Corrective Action: On 4/29/2025, an emergency purchase order was submitted and service request scheduled for vendor RF Technology to provide service to the egress door located on the west unit adjacent to the Coconut dining room. On 4/30/2025 RF Technology Inc. field service technician repaired the egress door. The door is equipped with delayed egress locking arrangements in accordance with NFPA 101. Identification of other residents potentially affected: All residents have the potential to be affected; however, based on inspection no residents were affected by this deficiency. All egress doors were inspected throughout the units to ensure compliance with NFPA 101 standards. No other egress doors were identified out of compliance. Measures: Director of Property Management and Maintenance team members were re-educated on conducting weekly egress door inspection and document on preventative maintenance sheet and report any non-functioning doors to supervisor immediately. Doors must be equipped with delay egress locking arrangements in accordance with NFPA 101. Monitoring: The Director of Property Management and Maintenance Assistants will complete weekly audits for 4 weeks and then monthly x two months to ensure compliance with NFPA 101 standards. Director of Property management will report the findings to the Quality Assurance Performance Improvement Committee Monthly X 3 months or until committee determines substantial compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Egress Door Required Multiple Actions to Unlock
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that an emergency egress door required more than one action to unlock due to a turn button lock, affecting 25 residents in one smoke compartment. The Maintenance Director confirmed the door had been in this condition for an extended period.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙