K0324 K324: Provide properly protected cooking facilities.
E

Noncompliant Cooking Equipment Installation

The Villa At Traverse PointTraverse City, Michigan Survey Completed on 05-07-2025

Summary

During an observation on May 7, 2025, surveyors identified that a shelf was protruding over the stove top burners in the facility's cooking area. This configuration was found to be noncompliant with NFPA 96, specifically section 10.2.7.3, as the shelf could obstruct the effectiveness of the hood suppression system in the event of a fire. The deficiency was confirmed through an interview with the Maintenance Director at the time of the observation. Approximately six occupants could be affected by this deficiency in the event of a fire emergency, as noted in the findings. No additional details about the medical history or condition of the occupants were provided in the report.

Plan Of Correction

LSC Annual Survey 5.7.25 K 324 Cooking Facilities Element 1 The fire suppression system over the range with the shelf was inspected by Fire Control, who adjusted the angle and type of the nozzles as well as adding. Fire Control then validated that this system was adequate for proper suppression. Element 2 A facility-wide audit does not reveal any other Ansul systems of suppression similar to the one mentioned, nor does it reveal any other obstructed sprinkler heads as part of the standard facility suppression system. Element 3 The maintenance director was educated on the regulations of tag K 324 in accordance with the NFPA 101 guidance. The regulatory maintenance schedule within TELS was reviewed and deemed appropriate, in addition to all other routine scheduled inspections and maintenance of the fire suppression systems. Element 4 The maintenance director will audit the Ansul system monthly in addition to all other routine TELS tasks to ensure nozzles are in proper place and working order. The results of all ongoing audits will be reviewed by the QAPI committee. The NHA is responsible for ongoing compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0324 citations
Commercial Cooking Hood Not Maintained Grease Tight per NFPA Standards
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility’s only commercial cooking hood was not maintained in accordance with NFPA 101 and NFPA 96 requirements. During a kitchen tour with the Maintenance Director, the hood was observed to be not grease tight due to missing fire-resistant caulk, and the Maintenance Director acknowledged this condition at the time of the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Kitchen Hood Inspections and Gas Appliance Restraints
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Surveyors found that the facility failed to maintain the kitchen fire suppression system in accordance with NFPA standards, with only one documented kitchen hood inspection in the prior year and no additional inspection records available despite multiple requests. During the kitchen tour, surveyors also observed that gas-fired appliances lacked restraints to prevent overextension of gas lines when moved for cleaning or service, a finding confirmed by the Maintenance Director. This deficiency had the potential to affect 22 of the 69 residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Kitchen Hood Suppression System
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation of the required semi-annual inspection for the kitchen hood suppression system, as confirmed during a review and interview with facility leadership. This deficiency affected one of two inspection reports.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Kitchen Suppression System Inspections and Cleanings
E
K0324 K324: Provide properly protected cooking facilities.
Short Summary

The facility did not provide documentation for a semi-annual kitchen suppression system inspection and two semi-annual kitchen hood cleanings, as confirmed during interviews with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Commercial Cooking Equipment Not Properly Secured
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Three gas-fed appliances on casters under the commercial cooking hood were found with restraint tethers attached but not secured to the wall attachments, as confirmed by the DOM during inspection. This failure to properly limit appliance movement resulted in non-compliance with NFPA 101, NFPA 96, and NFPA 54 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Unaware of Hood Fire Suppression System Operation
C
K0324 K324: Provide properly protected cooking facilities.
Short Summary

Kitchen staff were unable to identify or operate the manual activation for the kitchen hood fire suppression system, and this deficiency was confirmed by the administrator during interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙