K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Deficient Sprinkler System Maintenance and Testing

Shorepointe Nursing CenterSt. Clair Shores, Michigan Survey Completed on 04-15-2025

Summary

The facility failed to maintain and test its automatic sprinkler and standpipe systems in accordance with NFPA 25 requirements. Observations on multiple occasions revealed several deficiencies, including ceiling tile penetrations in the IT/Telecom Room and storage room, missing ceiling tiles in the Maintenance Office and laundry area, and missing or incomplete sprinkler components such as escutcheon rings and concealed covers in various rooms including a resident bathroom, Dietary Rest Room, Dialysis Treatment Room, and Conference Room. Additionally, dirty sprinkler heads were found behind the dryers in the laundry, and stock items were stored within 18 inches of a sprinkler head in the vestibule for dialysis storage. These issues were confirmed by the Maintenance Director during the survey. Further review of facility records showed a lack of documentation for the required quarterly flow tests for the automatic fire suppression system for two consecutive quarters. No evidence of these tests was provided to the surveyor by the time of exit. The combination of physical deficiencies and missing compliance documentation affected all 175 residents in the facility, as confirmed through interviews and record reviews with the Maintenance Director.

Plan Of Correction

K353 - Sprinkler System Maintenance and Testing 1. The facility failed to provide sprinkler system maintenance and testing as required by NFPA 25. a. The ceiling tile penetration on 2nd floor new side by IT/Telecom room has been replaced. b. The ceiling penetration in 2nd floor storage room with roof access has been replaced. c. Escutcheon plate in the 2nd floor room #235 has been replaced. d. The ceiling tile penetration in Maintenance Office by the IT equipment rack has been replaced. e. Dirty sprinkler heads behind the dryers have been cleaned. f. Missing sprinkler head in the Dietary restroom has been replaced. g. Escutcheon plate in the Dialysis den has been replaced. h. Missing sprinkler in the 1st floor conference room has been replaced. i. All combustibles and stock items within 18" have been removed from dialysis storage room. j. Missing ceiling tile above the washers in the laundry room has been replaced. 2. The maintenance director and staff will be educated on the importance of routine rounding to ensure the sprinkler heads have escutcheon plates and are clean, ceiling tiles maintain no breaches, and combustible/stock items maintain 18" from the ceiling. 3. To ensure continued compliance, the Maintenance director/designee will complete random audits 5 times a week for 4 weeks. Findings will be reported to the QAPI committee. 4. The facility Administrator will be responsible for assuring substantial compliance is attained through this plan of correction by 5/13/2025 and for sustained compliance thereafter.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙