K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
D

Egress Door Magnetic Locks Failed to Release Within Required Timeframe

Pines Nursing HomeMiami, Florida Survey Completed on 04-28-2025

Summary

During a Life Safety Survey at Pines Nursing Home, surveyors observed that the facility failed to maintain egress doors in accordance with NFPA 101 requirements. Specifically, two exit doors—one located by the Dialysis Room and another by Resident Room 20—were found to have magnetic locking mechanisms that did not release within the required 15 seconds. These observations were made during a walkthrough of the facility with the Maintenance Director present. The deficiency was confirmed through direct observation and was acknowledged by both the Maintenance Director and the Administrator during the exit conference. The report details that the doors in question are part of the required means of egress and are subject to strict standards regarding locking mechanisms, especially those that may delay or prevent rapid exit in an emergency. The delayed release of the magnetic locks did not comply with the standards set forth in NFPA 101, which stipulate that delayed-egress locking systems must release within 15 seconds to ensure safe evacuation. No specific residents or patients were directly involved or affected at the time of the survey, and there is no mention of any medical history or condition related to the deficiency. The findings are based solely on the physical inspection of the egress doors and staff interviews, with no additional incidents or adverse outcomes reported in connection with the deficiency.

Plan Of Correction

1. All occupants had the potential of risk but no one was harmed. Corrective action taken was designee from Maintenance or Housekeeping checked door for proper functioning upon daily exit until repair completed. 2. Upon discussion failure in the system was identified and intervention to address the deficit was implemented. During monthly QAPI meeting door check audit meant to track and monitor will be collected by Administrator for three months. Any adverse finding discovered through monitoring will be analyzed amongst the interdisciplinary team during QAPI gatherings. Audit presented to the committee is for recommendations purposes and to ensure department heads practice processes in applicable locations. 3. Facility obtained company on May 6, 2025 to inspect and service the door. 4. Magnet on each deficient door was replaced on May 20, 2025. 5. Maintenance Director or designee will review to assess if any additional task is needed to ensure compliance according to state and federal guidelines. 6. Maintenance team will perform daily scheduled door check. 7. Any identified deficiency will be reported to Administrator. Maintenance Director or Administrator will ensure proper party is secured to perform repair. 8. Maintenance team will perform preventive maintenance monthly. 9. On May 15 the Maintenance team was re-educated by the administrator on the proper procedure to check the door equipment.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0222 citations
Deficient Delayed Egress Door Signage and Function
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exit doors lacked the required signage with a contrasting background, and one door in the Service Hallway automatically reset when tested, both in violation of NFPA 101 standards. These deficiencies were observed during a fire safety tour and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Locking of Courtyard Exit Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors observed that a courtyard exit egress door was secured with a combination padlock, which did not meet NFPA 101 requirements. The issue was confirmed by facility leadership and had been previously identified earlier in the year.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Delayed Egress Doors
D
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that two delayed egress exits were not properly maintained: one exit failed to operate when tested, and another required excessive force to open. These issues were confirmed by the Maintenance Director during the inspection and discussed with facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

A 15-second delayed egress door by a resident room was found without the required signage indicating the door could be opened after 15 seconds, as required by NFPA 101. This deficiency was confirmed by the Maintenance Director and could affect all occupants in the affected wing.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Egress Door Required Multiple Actions to Unlock
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that an emergency egress door required more than one action to unlock due to a turn button lock, affecting 25 residents in one smoke compartment. The Maintenance Director confirmed the door had been in this condition for an extended period.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Signage on Delayed Egress Door
E
K0222 K222: Add doors in an exit area that do not require the use of a key from the exit side unless in case of special locking arrangements.
Short Summary

Surveyors found that a posted exit door from the solarium to the 600 wing was equipped with 15-second delayed egress hardware but lacked the required signage indicating, "PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS," as specified by NFPA 101. The Maintenance Director confirmed the absence of this signage during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙