K0347 K347: Properly provide smoke detection systems in areas open to corridors.
F

Failure to Maintain Smoke Detector Sensitivity Testing Records

West Shore Post AcuteAlameda, California Survey Completed on 05-06-2025

Summary

The facility failed to maintain required records of smoke detector sensitivity testing as mandated by NFPA 101 and NFPA 72 standards. During a record review and interview with the Maintenance Director, surveyors requested documentation showing that smoke detector sensitivity testing had been performed within the last two years. The facility was unable to provide any records of such testing, and the Maintenance Director stated that he believed the vendor had performed the test but would need to contact them for the records. No documentation was provided to the surveyors by the deadline given. This deficiency affected all 120 residents in all four smoke compartments of the facility. The lack of records means there was no evidence that the smoke detectors had been tested for sensitivity as required, which is necessary to ensure their proper functioning in the event of a fire. The surveyors noted that no previous records were available, and the required documentation was not submitted even after an opportunity was given to provide it.

Plan Of Correction

K347-Smoke Detection 1. Immediate action(s) taken for the resident(s) found to have been affected include: On 05/09/2025, the facility contracted with a certified vendor who performed smoke detector sensitivity testing on all applicable smoke detectors. The vendor's report confirmed all devices were within operational parameters. 2. Identification of other residents having the potential to be affected was accomplished by: All residents had the potential to be affected. 3. Actions taken/systems put into place to reduce the risk of future occurrence include: On 05/12/25, the Maintenance Director educated by the Administrator on the requirements and documentation for smoke detector sensitivity testing requirements per NFPA 72: 4. How the corrective action(s) will be monitored to ensure the practice will not recur: The Maintenance Director or designee will review testing schedules monthly to ensure smoke detector sensitivity testing is completed. Any issues identified will be immediately corrected. This plan of correction has been integrated into the facility Quality Assurance Committee, and the results of these audits will be reviewed quarterly until substantial compliance has been achieved. K 347

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0347 citations
Smoke Detection Deficiency in Room 406
D
K0347 K347: Properly provide smoke detection systems in areas open to corridors.
Short Summary

The facility failed to maintain smoke detection requirements in one smoke compartment. A broken and non-functional smoke detector was observed in room 406 on the fourth floor. This deficiency was confirmed through an interview with the Facility Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Battery-Operated Smoke Detectors
F
K0347 K347: Properly provide smoke detection systems in areas open to corridors.
Short Summary

The facility failed to maintain battery-operated smoke detectors, as they could not provide documentation for monthly testing and semi-annual battery replacement. The maintenance supervisor confirmed these deficiencies during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm System Documentation Deficiency
F
K0347 K347: Properly provide smoke detection systems in areas open to corridors.
Short Summary

The facility did not maintain compliance with fire safety regulations due to missing documentation for the most recent sensitivity test results of the fire alarm system. The maintenance manager confirmed the absence of this documentation during a survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Detector Obstruction in Kitchen Wash Room
E
K0347 K347: Properly provide smoke detection systems in areas open to corridors.
Short Summary

A smoke detector in the kitchen wash room on the first floor was found obstructed with a plastic cover and tape, failing to meet NFPA 101 standards. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Detectors
F
K0347 K347: Properly provide smoke detection systems in areas open to corridors.
Short Summary

The facility did not properly test and maintain battery-operated smoke detectors in resident rooms, as required by NFPA 101. Documentation lacked details such as make, model, and battery type, and only included monthly checkmarks. The manufacturer's manual required weekly testing, which was not documented. This affected all 114 smoke detectors, potentially impacting all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙