K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
D

Manual Fire Alarm Pull Stations Missing Protective Snap Bars

Mesa Glen Care CenterGlendora, California Survey Completed on 03-05-2025

Summary

Surveyors observed that two manual fire alarm pull stations in the facility were missing their protective plastic "snap" bars, which are designed to indicate the pull station is ready for use and has not been tampered with. One pull station missing the snap bar was located next to Resident Room 3, and another was found next to Nurse Station South. During interviews conducted at the time of observation, the Maintenance Supervisor stated that he believed patients were responsible for removing the snap bars. The absence of these snap bars means the pull stations were not maintained in proper working order and as designed, which could result in the pull stations being mistakenly activated and causing a false alarm. This deficiency affected two of three smoke compartments in the facility.

Plan Of Correction

K 342 Fire Alarm System - Initiation Correct Deficient Practice: On 03/7/25, Maintenance Supervisor (MS) called Delta Fire Equipment to get a replacement snap bar for the manual pull station. Snap bars were to be delivered and replaced on 03/10/25. Identify Others: On 03/10/2025, MS checked all manual pull stations to ensure all other manual pull stations are in proper working order and have the protective plastic "snap" bars. No other deficient practice was found. Systemic Changes: On 03/10/2025, the Administrator provided in-service education to Maintenance Supervisor regarding facility policy and procedures titled, "Maintenance Services" & "Fire Safety Inspections," indicating the maintenance department is responsible for maintaining the fire alarm system in good working order and the need for monthly fire safety inspections to be completed and forwarded to the administrator within 48 hours. MS or designee will complete the Mesa Glen Alarm Test Log on a monthly basis to ensure all manual pull stations are in proper working order and have the protective plastic "snap" bars in place. Any negative findings will be reported to the administrator and corrected immediately. Monitoring: Findings and trends from inspection rounds will be brought to the Quarterly Safety Committee meeting by MS until the Safety Committee has determined compliance has been sustained. Facility's Safety Committee will provide further recommendations as necessary. Completion Date: 3/28/2025.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0342 citations
Smoke Detector Failed to Initiate Fire Alarm During Testing
D
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A smoke detector outside a resident room failed to activate the fire alarm system during two separate tests with artificial smoke. Staff could not determine the cause at the time, but noted the proximity of an AC vent, which may have affected the detector's function. This issue impacted 14 residents in one smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Blocked Fire Alarm Pull Station in Dining Room
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull station was observed to be blocked in the Delaware dining room near the courtyard doors, making it inaccessible and in violation of NFPA 101 requirements for manual fire alarm system initiation. This was confirmed by the Facilities Director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Access to Fire Alarm Pull Stations
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

Surveyors found that access to two fire alarm pull stations was blocked by portable nurse worktables and a dirty linen cart, with the Maintenance Supervisor confirming staff awareness of proper storage procedures. The facility's policy requires maintenance of safe and accessible equipment, but these obstructions were not removed as required.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Pull Station Obstructed by Storage Items
E
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to maintain the initiation of the required fire alarm system on one level. A fire alarm pull station in the Activities Department was blocked by storage items, making it inaccessible. This was confirmed during an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Box Obstruction in Kitchen
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

A fire alarm pull box in the facility's kitchen was obstructed by a steel table used as an extension of the dishwashing machine table, blocking access to the alarm. This deficiency was confirmed during an interview with the AIT and reported at the Life Safety Code exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Alarm Manual Pull Stations Obstructed
F
K0342 K342: Have a complete alarm system manually initiated and initiated by fire sprinkler system connection.
Short Summary

The facility failed to ensure fire alarm manual pull stations were accessible, as required by NFPA 72:2010. Observations revealed that a pull station in the dining room was blocked by a table, and another in the physical therapy room was obstructed by wheelchairs and a bed. This deficiency could potentially affect all 83 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙