K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
F

Sprinkler System Maintenance and Testing Deficiencies

California Home For The AgedFresno, California Survey Completed on 03-26-2025

Summary

The facility failed to maintain its automatic sprinkler system in accordance with NFPA 25 and NFPA 13 standards. During a tour and interviews with staff, surveyors observed that inspector test valves (ITVs) in the medicine room by nurses station 3 and in the courtyard were missing required signage. Staff interviewed were unaware of the missing signs. Additionally, a sprinkler located in the storage closet next to nurses station 3 was found to be covered in dust, and staff were not aware of this condition. Further, when the waterflow was tested at the ITV in the medicine room by nurses station 3, it took 116 seconds for the alarm to initiate after the valve was fully opened, which exceeds the acceptable time for waterflow alarm activation. Staff interviewed were unaware of the reason for this delay. These deficiencies affected all 103 residents in the facility across five smoke compartments.

Plan Of Correction

K 353: How will the corrective action be accomplished for those residents found to have been affected by the deficient practice? The facility has not identified any residents affected by the deficient practice but recognizes that all residents have the potential to be affected. The facility contracted with MS Fire, a qualified contractor, to inspect each identified area of deficiency, and to determine and obtain the necessary signage for each Inspector Test Valve and all Auxiliary Drain valves. During this inspection, the valve located in the medicine room by station 3 was properly identified as an Auxiliary Drain Valve and not an Inspector Test Valve. Signage indicating that this is an Auxiliary Drain valve was placed during the inspection done on 04/02/2025. As this was identified as an Auxiliary Drain valve and not an Inspector Test Valve, MS Fire has corroborated during their inspection that the water flow expected of this valve was in working order and it is not expected to perform as an Inspector Test Valve, alarming in no more than 90 seconds. This is because Auxiliary Drain valves do not have the restricted head on the discharge pipe to correctly stimulate a fire sprinkler activation as an Inspector Test Valve would, and therefore this is why it took longer than 90 seconds to alarm. During this same inspection, the valve located in the courtyard was properly identified as an Auxiliary Drain Valve and not an Inspector Test Valve. Signage indicating that this is an Auxiliary Drain Valve was placed during the inspection done on 04/02/2025. Two other correctly identified Inspector Test Valves were tested during the survey process and performed within regulatory requirements, alarming in less than 90 seconds. The sprinkler located in the storage closet next to Nurses Station 3 was cleaned of dust on 3/26/25 by the Maintenance Lead and reinspected by MS Fire on 04/02/2025. How will the facility identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken? The facility recognizes that while no residents were identified to have been affected by the deficient practice, all residents have the potential to be affected. The same corrective actions as listed above are the corrective actions taken to eliminate the potential risk to the residents. What measures will be put into place or what systemic changes will the facility make to ensure that the deficient practice does not recur? The Maintenance Director in-serviced all maintenance personnel on the locations and appropriate signage required for Inspector Test Valves and Auxiliary Drain valves. Also included in this same in-service was the importance of inspecting and cleaning sprinkler heads to keep them free of dust. The facility utilizes TELS Building Management System for all Maintenance related inspections or tasks. A monthly in-house fire sprinkler inspection task was added to the Maintenance TELS system to include checking fire sprinkler heads for dust and Auxiliary Drain Valves and Inspector Test Valves for appropriate signage. Any findings will be immediately corrected and reported by the Maintenance team member completing the task to the Maintenance Lead and/or Director. Housekeeping staff was in-serviced by the Hospitality Director/Environmental Services Director on how to clean fire sprinkler heads to keep them free of dust. How does the facility plan to monitor its performance to make sure that the corrective actions are implemented and achieved, the solutions are sustained, and that the corrective actions taken are evaluated for effectiveness through integrations into the facility's Quality Assurance system? The Facility Maintenance Director shall review monthly in-house sprinkler inspection task reports for completion and findings. What measures will be put into place or what systemic changes will the facility make to ensure that the deficient practice does not recur? The Maintenance Director in-serviced all maintenance personnel on the locations and appropriate signage required for Inspector Test Valves and Auxiliary Drain valves. Also included in this same in-service was the importance of inspecting and cleaning sprinkler heads to keep them free of dust. The facility utilizes TELS Building Management System for all Maintenance related inspections or tasks. A monthly in-house fire sprinkler inspection task was added to the Maintenance TELS system to include checking fire sprinkler heads for dust and Auxiliary Drain Valves and Inspector Test Valves for appropriate signage. Any findings will be immediately corrected and reported by the Maintenance team member completing the task to the Maintenance Lead and/or Director. Housekeeping staff was in-serviced by the Hospitality Director/Environmental Services Director on how to clean fire sprinkler heads to keep them free of dust.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0353 citations
Missing Documentation for Required Sprinkler System Inspections
C
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for its fire sprinkler system. During review and interview, the facility could not provide records of semi-annual inspections for valve supervisory switches or annual inspections for control valves. The maintenance supervisor confirmed that these sprinkler system inspection records were not available when requested by surveyors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Sprinkler System Testing and Fire Drill Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that the facility failed to maintain required documentation for multiple fire protection system tests and inspections, including the annual fire hydrant flow test, the five-year GPM test of the hydrant, the five-year internal inspection of the fire riser, and the five-year hydrostatic test of the FDC, as required by NFPA 101 and NFPA 25. In addition, the facility lacked records of required fire drills for each shift per quarter, with missing drills for one quarter’s third shift and for the second and third shifts of the last quarter of the prior year. The Maintenance Director acknowledged that these records were not available.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 5-Year Internal Sprinkler System Inspection Report
D
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors determined that the facility did not maintain required documentation for its automatic sprinkler system. Record review showed the sprinkler system was past due for the mandated 5-year internal inspection, and the facility could not produce the most recent 5-year inspection report. During interview, the Maintenance Director confirmed that this inspection report was missing, and the deficiency was cited as affecting the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Sprinkler Inspection Records and Obstructed Exterior Sprinkler Head
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors found that required sprinkler system inspection documentation was incomplete, with only three quarterly reports available and the 2nd quarter annual sprinkler report missing. During observation of the exterior car port, one of six sprinkler heads was obstructed by underside aluminum paneling. The Administrator and Maintenance Director confirmed both the missing documentation and the obstruction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Support of Sprinkler Piping by Electrical Conduit in Two Smoke Compartments
E
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility did not maintain its automatic sprinkler system in accordance with NFPA standards when electrical MC wire conduit was found resting directly on sprinkler piping above ceiling tiles in the elevator lobby areas on two separate floors, affecting two of fifteen smoke compartments. The Facility Administrator and Director of Maintenance acknowledged these sprinkler system deficiencies during interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Sprinkler System Inspection Documentation
F
K0353 K353: Inspect, test, and maintain automatic sprinkler systems.
Short Summary

Surveyors identified that the facility failed to maintain required inspection and testing of its automatic sprinkler system in accordance with NFPA standards. Record review showed only one documented sprinkler inspection within the prior year, and no additional inspection records were produced despite multiple requests during the survey. The Maintenance Director confirmed that no other sprinkler inspection documentation was available, indicating that ongoing required inspections were not documented for all residents in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙