K0711 K711: Provide a written emergency evacuation plan.
F

Deficient Fire Safety Training and Evacuation Plan Implementation

Regency On The Lake - Fort GratiotFort Gratiot, Michigan Survey Completed on 07-03-2025

Summary

The facility failed to ensure that there was a written plan for the protection and evacuation of all residents in the event of an emergency, and did not provide periodic staff training consistent with their expected roles as outlined in the Fire Safety Plan. During an observation and interview, two out of three dietary staff members were unable to correctly describe the procedures for activating the installed range hood suppression system, and one dietary staff member could not identify which extinguisher should be used on a grease fire. These deficiencies were confirmed by both the Maintenance Director and the Dietary Manager during the observation. The lack of proper staff instruction and knowledge could affect all 128 residents in the event of a fire involving the deep fat fryer or kitchen range equipment.

Plan Of Correction

Element I: The dietary staff was given education regarding the procedure for activating the suppression system and which fire extinguisher to use for a grease fire. Element II: All residents and staff have the potential to be affected by the deficient practice. Element III: The fire prevention plan policy was reviewed by the IDT and deemed appropriate. All dietary staff will be educated on the fire prevention plan with emphasis on the suppression system and the appropriate fire extinguisher to use for a grease fire. The dietary supervisor/designee will ensure new hires are educated on the first day of training in the kitchen. In addition, the fire prevention plan has been added to the staff meeting agenda. Element IV: The dietary supervisor/designee will conduct random audits to ensure the staff can appropriately verbalize the use for fire extinguishers and suppression system. These audits will be weekly for 4 weeks then monthly for 2 months until compliance has been maintained. The results will be brought to the QAPI meetings. Element V: The dietary supervisor/administrator are responsible for continued compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0711 citations
Failure to Activate Fire Alarm During Electrical Fire
F
K0711 K711: Provide a written emergency evacuation plan.
Short Summary

During an electrical fire in the main panel room, staff failed to activate the manual fire alarm as required by facility policy. Instead, staff called 911 and notified others verbally, but did not use the nearest manual pull station, resulting in the fire alarm not being triggered and the facility not being fully alerted.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Evacuation Map in Corridor
E
K0711 K711: Provide a written emergency evacuation plan.
Short Summary

Surveyors found that the required evacuation map was missing in the Maple Ridge corridor, which is necessary for identifying locations and evacuation routes. This deficiency was confirmed with the Maintenance Director and could impact 26 of 64 residents during an emergency evacuation.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Kitchen Staff Lacked Training on Grease Fire Response
D
K0711 K711: Provide a written emergency evacuation plan.
Short Summary

Two kitchen staff members were found to be unaware of proper response protocols for grease fires and reported not having received training on this topic. This deficiency was observed during a facility tour and interview with the DOM and Kitchen Lead Staff, affecting one of four smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Train Staff on Emergency Evacuation Procedures
F
K0711 K711: Provide a written emergency evacuation plan.
Short Summary

Nursing staff on an upper floor reported not receiving training on evacuation procedures for moving residents to the ground level when elevators are unavailable or during a fire. This was confirmed by the Maintenance Director, indicating a lack of compliance with required emergency preparedness training.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Communicate Emergency Evacuation Plan Amid Inoperable Sprinkler System
F
K0711 K711: Provide a written emergency evacuation plan.
Short Summary

The facility did not ensure staff were informed or educated about changes in fire response procedures after a portion of the sprinkler system was found inoperable, with only six active heads in the attic. Both a CNA and the ADON were unaware of the system's status, and the deficiency was confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙