K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
E

Failure to Maintain Smoke Barrier Integrity per NFPA 101

Lost Creek Rehabilitation And Nursing CenterLima, Ohio Survey Completed on 06-04-2025

Summary

The facility failed to maintain fire and smoke barriers in accordance with NFPA 101-2012 Edition, Section 19.3.7.3 and Section 8.5.6.2. During a facility tour, surveyors observed multiple penetrations in smoke barriers that were improperly sealed with non-fire-rated, rubber-like materials. These penetrations included aluminum conduits and black pipes located in the interstitial spaces between the ceiling and drop ceiling above several 20-minute fire-rated double corridors leading into various halls, including the 100, 200, 300, and 400 Halls, as well as the Service Hall. Additionally, one 3-inch black pipe was found completely unsealed in the attic space above a fire-rated double corridor leading into the attic. The materials used to seal the other penetrations were not fire-rated and did not meet the requirements for restricting the transfer of smoke as specified by the referenced NFPA standards. The Regional Maintenance Director confirmed at the time of discovery that he was unsure of the type of material used to seal the pipes. These deficiencies were identified during direct observation and staff interviews, and the findings were confirmed by facility maintenance leadership. The report notes that these failures had the potential to affect all 39 residents in the facility, as the integrity of the smoke barriers was compromised by the use of improper sealing materials and the presence of unsealed penetrations.

Plan Of Correction

Tag: K 0372 Both the pipe and conduits between the ceiling and drop ceiling above the fire-rated double corridor leading into 100 hall, 200 hall, 300 hall, 400 hall, service hallway, and into the attic space were repaired with fire-rated caulk on or before 6/20/25. There was no other conduit or pipes found to have penetrations not properly sealed. Administrator educated maintenance director on NFPA 101 subdivision of building spaces - smoke barrier construction on 6/16/25. Maintenance director or designee will audit pipes and conduits for penetration monthly x 3 months. Audits will be submitted to the QAPI committee for review and recommendations. K 0372

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure of Fire Doors to Close Compromises Smoke Barrier Integrity
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors observed that double rated fire doors on the 3rd floor did not close when released from magnetic hold open devices, resulting in smoke barriers not meeting the required 1/2-hour fire resistance rating. This deficiency was confirmed by the maintenance director and could impact 40 occupants by allowing smoke, heat, and fire to pass between compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙