K0363 K363: Install corridor and hallway doors that block smoke.
F

Failure to Maintain Smoke-Resistant Corridor Doors

Pinnacle Care Of Battle CreekBattle Creek, Michigan Survey Completed on 05-08-2025

Summary

Surveyors observed that the facility failed to ensure that doors protecting corridor openings were capable of resisting the passage of smoke as required by NFPA 19.3.6.3. Specifically, on three separate occasions, it was found that the North Dining Room door across from resident room 125 was missing a latch and would not properly latch when tested, and the North Dining Room door across from resident room 107 also would not latch. Additionally, Resident Room 125 was found to have a 2-inch gap between the door and the floor, exceeding the maximum allowable clearance. These deficiencies were confirmed through direct observation and interview with the Facility Maintenance Director at the time of the survey. The report does not mention any specific residents' medical history or conditions at the time of the deficiency, nor does it indicate any immediate harm, but it documents the failure of the facility to maintain corridor doors in accordance with fire safety regulations.

Plan Of Correction

K363 1. The Maintenance Director and/or designee will repair the North Dining Room doors to ensure a positive latch, along with the gap in resident room 125 door. 2. The Administrator will review regulation K363 and provide education to the Maintenance team on the requirements. 3. The Maintenance Director and/or designee will conduct weekly rounds of doors protecting corridor openings to ensure no gaps and that doors close to a positive latch. Results of the audits will be brought to the Quality Assurance Performance Improvement meeting monthly for review. The Committee will be responsible for any changes to the auditing process. 4. The Administrator is responsible to attain and maintain compliance. Completion date for compliance will be 06.20.25.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0363 citations
Failure of Corridor Door to Latch Properly
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that a corridor door to a resident room on one floor failed to latch into the frame when tested, meaning it did not meet NFPA 101 requirements for positive latching of corridor doors. The Facilities Manager and Facility Life Safety staff confirmed during interview that this corridor door did not latch properly.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Multiple Corridor Door Deficiencies Impacting Smoke and Fire Protection
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors identified several corridor door deficiencies, including doors that failed to latch, lacked smoke tight integrity, and had missing locksets, across multiple floors. These issues were confirmed by facility leadership during the exit conference.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Properly Latching Corridor Doors
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two corridor doors, one on the third floor and one on the second floor, did not latch when tested, affecting two smoke compartments. The Facility Administrator and Maintenance Director confirmed these deficiencies, which were not in compliance with fire and smoke protection requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Positive Latching of Corridor Door
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

A corridor door leading to the Patio Lounge failed to positively latch within the door frame, as observed and confirmed by the Director of Maintenance. This deficiency affected one of twelve smoke compartments and did not meet NFPA 101 and CMS requirements for corridor door latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Corridor Doors for Smoke Resistance and Latching
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that corridor doors to two resident rooms did not close and latch properly, as confirmed by the facility's Administrator and Maintenance Director. This deficiency affected one of five smoke compartments and did not meet regulatory requirements for smoke resistance and positive latching.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Corridor Doors Blocked Open with Wedges
E
K0363 K363: Install corridor and hallway doors that block smoke.
Short Summary

Surveyors found that two resident rooms had wooden door wedges holding corridor doors open, preventing them from closing as required for fire safety. Facility staff confirmed that the wedges impeded proper door closure.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙