K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
E

Electrical System Deficiencies: Exposed Wiring and Inaccessible Panels

Holland Center For Rehabilitation And NursingHolland, Pennsylvania Survey Completed on 07-16-2025

Summary

Surveyors observed that the facility failed to maintain proper protection of electrical wiring in multiple areas. Specifically, an open junction box with exposed wiring was found in the basement phone room. Additionally, in the storage room across from the Health Care Administrator's office, two electrical panels (DP 2 and DP 4) were blocked by storage items within three feet, and one of the panels (DP 4) had a broken latch, making it difficult to open. During a follow-up onsite revisit, it was determined that the issue with the missing latch on the DP 4 electrical panel door had not been corrected, and the panel was still not secured properly. These deficiencies were confirmed during exit interviews with the Administrator and Maintenance Director. No information about residents or their medical conditions was included in the report.

Plan Of Correction

1) The electrical panel labeled DP 4 has been repaired so that it can latch and be easily opened. Storage has been removed from in front of electrical panel DP 2 and DP 4. 2) Other electrical panels have been checked to ensure that there is no storage and that the latch can close and be easily opened. 3) The Maintenance Director and/or designee will perform audits weekly, for four weeks and monthly for two months to ensure that the electrical panels can latch and easily open, and that there is no storage within three feet of the panels. Results of the audits will be reported to QAPI.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0911 citations
Open Breaker Slot Found in Generator Room Electrical Panel
D
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors observed that the generator room contained an electrical breaker panel labeled "Panel HC" with an open breaker slot, indicating the electrical system was not maintained per NFPA 70 and NFPA 99 requirements. During an interview, the maintenance supervisor confirmed this electrical system deficiency in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Panel Blocked by Cart in Nurse Station Supply Closet
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

An electrical panel inside the nurse station supply closet was found to be blocked by a large cart, making it inaccessible in violation of NFPA 70 requirements. This was confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Wiring Protection Deficiencies Identified
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors identified multiple deficiencies in the protection of electrical wiring, including broken receptacle cover plates, open junction boxes, open wires not ending in a junction box, and unsecured electrical outlets in two smoke compartments. These issues were confirmed by facility leadership and cited as non-compliant with NFPA 70 and NFPA 99 standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical System Maintenance Deficiencies Identified
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Surveyors found that a receptacle near an A-bed was missing a cover and a reading light over another A-bed had exposed, non-terminated wiring hanging from the underside of the cover. These electrical system deficiencies were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multipliers for Heat Tape
D
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

Heat tape installed on the building was found plugged into outlet multipliers outside the main entrance, which was confirmed as a deficiency by the maintenance supervisor during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical System Deficiencies Found in Facility
E
K0911 K911: Meet requirements for the installation and maintenance of electrical systems.
Short Summary

The facility failed to maintain electrical system requirements, with unsecured junction boxes found above the ceiling on the first floor and exposed wiring in the Hood Mechanical Room. These deficiencies were confirmed during an exit interview with the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer