K0920 K920: Ensure proper usage of power strips and extension cords.
F

Improper Use of Extension Cords and Power Strips for Window AC Units

Cliveden Nursing And Rehabilitation CenterPhiladelphia, Pennsylvania Survey Completed on 08-12-2025

Summary

Surveyors observed that throughout the facility, on each floor, multiple window air conditioning (AC) units were being used in place of the originally installed P-Tec units. These window AC units had been retrofitted by removing the factory-supplied GFCI power cords, then cutting, splicing, and attaching extension cords. This modification eliminated the AC units' original electrical protections. Additionally, one window AC unit in the Dietary Director's office was found plugged into a power strip, which is not permitted for this type of equipment. Interviews with the Administrator, Regional and local Maintenance Director, and the VP of Building Operations confirmed that power strips and extension cords were used to modify window AC units, resulting in the removal of the AC units' electrical protections and the attachment of heat-drawing equipment to power strips. These actions were found to be in violation of NFPA 101 and related standards, as extension cords and power strips were improperly used as substitutes for fixed wiring and permanent outlets.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
C
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unauthorized Use of Extension Cords and Surge Protectors
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that extension cords and surge protectors were being used in multiple rooms to power phone chargers and medical devices, in violation of NFPA 101 and related standards. Facility leadership confirmed these unauthorized devices were in use during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙