K0211
E

Obstructed Means of Egress Due to Improperly Stored Isolation Carts

Heartwood Lodge Trinity HealthSpring Lake, Michigan Survey Completed on 06-10-2025

Summary

Surveyors observed that aisles, passageways, and corridors were not maintained free of obstructions as required by Chapter 7 of the Life Safety Code. Specifically, isolation carts without wheels attached were found stored in the corridor outside residents' rooms 121 and 122 in the 100 hall, and outside room 213 in the 200 hall. These findings were confirmed during interviews with maintenance staff present at the time of observation. The deficiency was identified during a walkthrough on June 10, 2025, and could potentially affect 18 occupants within the smoke compartment in the event of an emergency evacuation. No information regarding the medical history or condition of the residents in the affected areas was provided in the report.

Plan Of Correction

Element 1 - Environmental service staff removed all isolation carts without wheels stored in the corridor outside resident rooms 121 and 122 located at 100 hall and isolation carts without wheels stored in the corridor outside resident room 213 located at 200 hall with isolation carts with wheels to meet Means of Egress compliance. Element 2 - The Environmental Services Director or designee inspected all remaining isolation carts to ensure compliance with Means of Egress. Element 3 - Environmental Services Director or designee will complete monthly inspections on aisles, passageways, corridors, and exit locations for isolation carts being stored without wheels for 3 months to ensure compliance with NFPA 101 Chapter 7. Element 4 - The Environmental Services Director or designee will report audit findings to the Quality Assurance / Performance Improvement (QAPI) Committee quarterly x 3 with further monitoring per QAPI recommendations. Any identified issues will trigger retraining and/or corrective action. Element 5 - The Nursing Home Administrator is responsible for maintaining compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0211 citations
Staff Inability to Operate Locked Smoking Patio Exit Gate
E
K0211
Short Summary

Surveyors found that staff assigned to the designated smoking patio did not have the necessary knowledge to operate the electronic magnetic locked exit gate leading to the public way. During a fire safety tour, a CNA serving as the Smoking Area Attendant repeatedly entered the correct access code but could not open the gate because she pulled instead of pushed, demonstrating that staff were not fully able to utilize this means of egress as required by NFPA 101. The Administrator and Maintenance Director confirmed these observations, and the deficiency was noted as affecting residents who smoke.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Means of Egress Obstructed by Two-Step Lock on Office Door
C
K0211
Short Summary

A two-step lock, including a dead bolt, was observed on the environmental services office door next to the salon, potentially impeding emergency egress. This was confirmed by the administrator and maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing 'Not an Exit' Signage on Courtyard Door
E
K0211
Short Summary

A door leading to an enclosed courtyard in the Ivy Wing South Living Room was observed without a 'Not an Exit' sign, making it possible to mistake the door for an exit. This lack of signage was confirmed by facility leadership and resulted in noncompliance with NFPA 101 requirements for maintaining clear means of egress.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Insufficient Headroom in Basement Corridor
B
K0211
Short Summary

Surveyors observed that the headroom in a basement corridor was approximately 6 feet 2 inches, which is below the required 6 feet 8 inches for means of egress. This was confirmed by the Administrator and affected one of two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed Emergency Exit Due to Chained Patio Gate
F
K0211
Short Summary

A gate leading from the patio area was found chained shut, blocking a designated emergency exit. This obstruction was observed and confirmed by the Maintenance Director, preventing proper egress in case of emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Obstructed and Inaccessible Emergency Exits Identified
E
K0211
Short Summary

Surveyors found that multiple emergency exits were inaccessible or obstructed, including a sealed exterior door, a corridor blocked by dialysis transport chairs, and a stuck exit door from the main dining room. These issues were confirmed by the maintenance director during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙