K0371 K371: Have properly sized and located compartments to protect residents from smoke.
B

Lack of Required Smoke Barrier on Resident Sleeping Floor

Kadima Rehabilitation & Nursing At PalmyraPalmyra, Pennsylvania Survey Completed on 07-29-2025

Summary

The facility failed to provide at least two smoke compartments on each resident sleeping floor containing 30 or more resident beds, as required by NFPA 101. During an observation, it was found that the resident sleeping floor did not have a smoke barrier, which was confirmed by the Administrator during an interview. This deficiency affects one of two floors within the component and was identified through direct observation and staff confirmation. No additional details regarding specific residents, their medical history, or their condition at the time of the deficiency were provided in the report.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0371 citations
Smoke Compartment Size Exceeds NFPA 101 Standards
B
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have a smoke compartment on the 1st floor that exceeded the NFPA 101 maximum size of 22,500 square feet, as observed during a survey. This deficiency was confirmed in an exit interview with the CEO and Director of Campus Services.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Complete Smoke Compartmentalization
F
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility did not provide a smoke barrier map showing complete compartmentalization by smoke barriers throughout the building, as required by code. The map lacked details of smoke barriers separating compartments from outside wall to outside wall, and this was confirmed by Facility Maintenance during record review.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Compartment Size Exceeds NFPA 101 Standards
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have smoke compartments exceeding the maximum allowable size of 22,500 square feet in the 400 wing and First Floor, affecting two of four smoke compartments. This was confirmed through observation, document review, and interviews with facility staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Compartment Size Exceeds Maximum Allowance
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have a smoke compartment in the C Wing that exceeded the maximum allowable area of 22,500 square feet, as per NFPA 101 standards. This deficiency was confirmed during an observation and document review, affecting one of four smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Smoke Barriers in Facility
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility did not meet NFPA 101 standards for smoke barriers, failing to install and maintain them to form at least two smoke compartments on every sleeping floor with a capacity of 30 or more patient beds. Observations revealed incomplete smoke barriers throughout the building, confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Facility Exceeds Maximum Smoke Compartment Size
C
K0371 K371: Have properly sized and located compartments to protect residents from smoke.
Short Summary

The facility was found to have three smoke compartments exceeding the maximum allowable size of 22,500 square feet. Smoke compartments one, two, and five were identified as non-compliant during a document review and interview. This issue was confirmed in an exit interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙