K0917 K917: Ensure electrical receptacles or cover plates have distinctive color or marking.
D

Medication Refrigerator Not Connected to Critical Branch and EES Maintenance Documentation Lacking

Nspire Healthcare TamaracTamarac, Florida Survey Completed on 01-22-2026

Summary

The facility failed to ensure that electrical receptacles serving medication preparation areas, specifically those used for medication refrigerators, were connected to the critical branch of the Essential Electrical System (EES) and were not distinctly marked as required by NFPA 99. During a fire safety tour, it was observed that a medication refrigerator was not plugged into a receptacle powered by the critical branch, and the required distinctive color or marking was absent. This deficiency was acknowledged by the Regional Maintenance Director during the observation and was reviewed with facility leadership at the exit conference. Photographic evidence was obtained to document the finding. Additionally, the facility did not maintain proper documentation for the maintenance and testing of the EES, including the generator and associated equipment. Required records for weekly inspections, monthly load exercises, and other scheduled maintenance activities were not provided during the record review with the Regional Director of Plant Operations. The lack of documentation means that the facility could not demonstrate compliance with NFPA 99, NFPA 110, and related standards for ensuring the reliability of emergency power systems. These deficiencies affect all residents who receive refrigerated medications from the affected medication room, as well as all residents and staff who rely on the facility's emergency electrical systems. The findings were based on direct observation, staff interviews, and record reviews conducted by surveyors during the inspection.

Plan Of Correction

Corrective Action for Affected Residents: The room medication refrigerator will be correctly tied into critical branch breaker to ensure it is supplied by the critical branch of the essential electrical system along with a distinctly marked critical branch receptacle, ensuring uninterrupted power during normal and emergency conditions for residents receiving refrigerated medications. Identification of Other Residents Potentially Affected: The facility conducted a review of all medication refrigerators and receptacles supplied by the essential electrical system, including medication preparation areas, to verify proper connection to and identification of critical branch power. Measures to Prevent Recurrence: All medication refrigerators will be verified to be connected to and powered by the critical branch. The Maintenance Director was educated on NFPA 99 requirements related to essential electrical system branch identification and medication refrigeration power sources. Monitoring/Quality Assurance: Compliance will be reviewed by the Administrator or designee through the facility's QAPI program, and corrective action will be taken immediately if deficiencies are identified. Corrective Action for Affected Residents: The facility will correct deficiencies related to generator maintenance and testing documentation to ensure the Essential Electrical System (EES) is maintained in accordance with NFPA requirements. Specifically: Weekly generator inspection forms provided by TELs will be updated to include battery voltage readings for both generator batteries. Monthly generator testing forms will be updated to include battery conductance testing for sealed batteries. Monthly generator load testing documentation will reflect testing at a minimum of thirty percent (30%) of nameplate capacity, and a four (4) hour continuous load bank test was completed in [date] and will be conducted annually, with the next test due [date], and annually thereafter. These actions will ensure reliable emergency power is available to protect residents, staff, and essential services. Identification of Other Residents Potentially Affected: The facility will conduct a review of all generator maintenance and testing records to ensure compliance with NFPA 110 requirements, including weekly inspections, monthly testing, battery monitoring, and extended load testing. Measures to Prevent Recurrence: Generator inspection and testing forms provided by TELs will be permanently revised to include required weekly battery voltage readings and monthly battery conductance testing. The four (4) hour load bank test will be scheduled annually, with the next test due [date], and annually thereafter. The Maintenance Director will be educated on NFPA 99 and NFPA 110 requirements related to generator testing, battery monitoring, and documentation. Monitoring/Quality Assurance: Generator logs will be reviewed monthly by leadership and monitored through the QAPI program. Corrective Action for Affected Residents: The room medication refrigerator will be correctly tied into critical branch breaker to ensure it is supplied by the critical branch of the essential electrical system along with a distinctly marked critical branch receptacle, ensuring uninterrupted power during normal and emergency conditions for residents receiving refrigerated medications. Identification of Other Residents Potentially Affected: The facility conducted a review of all medication refrigerators and receptacles supplied by the essential electrical system, including medication preparation areas, to verify proper connection to and identification of critical branch power. Measures to Prevent Recurrence: All medication refrigerators will be verified to be connected to and powered by the critical branch. The Maintenance Director was educated on NFPA 99 requirements related to essential electrical system branch identification and medication refrigeration power sources. Monitoring/Quality Assurance: Compliance will be reviewed by the Administrator or designee through the facility's QAPI program, and corrective action will be taken immediately if deficiencies are identified.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0917 citations
Medication Refrigerator Not Connected to Critical Branch Receptacle
D
K0917 K917: Ensure electrical receptacles or cover plates have distinctive color or marking.
Short Summary

Surveyors found that a medication refrigerator in the South Wing medication room was plugged into a receptacle that was not distinctly marked or supplied from the critical branch of the essential electrical system, as required by NFPA 99. This issue was identified for 1 of 5 sampled medication refrigerators and affected residents whose medications were stored in that unit. The Administrator and Maintenance Director observed and acknowledged the noncompliant receptacle configuration during the fire safety tour, and the findings were later reviewed with them along with photographic evidence.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Emergency Electrical Receptacle Markings Worn Off
D
K0917 K917: Ensure electrical receptacles or cover plates have distinctive color or marking.
Short Summary

A facility failed to maintain the required distinctive color markings on an emergency electrical receptacle in the dining room, as most of the red coloring had been worn off by residents' wheelchairs. The Maintenance Supervisor confirmed the deficiency, noting the receptacle should be red to indicate its connection to the life safety emergency system.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Distinctly Mark Emergency Power Outlets
E
K0917 K917: Ensure electrical receptacles or cover plates have distinctive color or marking.
Short Summary

Surveyors found that electrical outlets supplied by the emergency generator in one area of the facility were not marked with a distinctive color as required by NFPA 99. The maintenance director confirmed that some corridor outlets on emergency power were not properly identified, which could lead to staff not using them during a power outage.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙