K0354 K354: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
E

Sprinkler System Out of Service Due to Equipment Failure

Rolling Fields, IncConneautville, Pennsylvania Survey Completed on 12-22-2025

Summary

A deficiency was identified when the facility failed to maintain compliance with sprinkler system regulations for one of its two dry sprinkler systems. On observation, system #1 was found to be out of service due to a malfunctioning air compressor, and the backup air compressor was not operational or connected to a power source. There was no documentation provided regarding the extent or duration of the system being out of operation. The maintenance technician confirmed that the dry system was out of service at the time of the survey. Subsequent surveys revealed that the deficiency remained uncorrected, as the facility had not completed the necessary repairs or inspections to restore the sprinkler system to service. The facility had received a bid from a vendor but had not secured funding or payment to proceed with the repairs. During this period, the facility maintained a continuous fire watch as the sprinkler system remained nonfunctional.

Plan Of Correction

1. Absolute Fire Protection has been contacted to ensure that any and all necessary parts needed to fix the malfunctioning air compressor will be ordered and installed, so that the dry sprinkler system can be turned back on prior to the "substantial compliance" date of 1/30/2026. Documentation WAS provided to the extent and duration of the dry system being out of operation in the form of "fire walk" documentation, from the day the system went down through present day. 2. The Administrator will assist the Environmental Services Director in ensuring that Absolute Fire Protection is contacted for service and that payment will be secured for any and all necessary parts to ensure the malfunctioning air compressor is operational, which will then allow for the dry sprinkler system to be turned back on. 3. The results of these corrective actions will be reviewed at the facility's next two quarterly Quality Assurance Performance Improvement meetings to ensure compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0354 citations
Lack of Fire Watch Policy for Sprinkler System Outage
C
K0354 K354: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Short Summary

A review of facility documentation and staff interviews revealed the absence of a fire watch policy for periods when the sprinkler system is impaired or out of service for more than ten hours. This deficiency was confirmed by the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Incomplete Fire Watch Policy for Sprinkler System Outage
C
K0354 K354: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Short Summary

A review of facility records and staff interviews revealed that the fire watch policy lacked required language specifying that a fire watch must be implemented if the sprinkler system is out of service for more than ten hours. This omission affected all residents and smoke compartments in the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Provide Fire Watch and Staff Notification During Sprinkler System Outage
F
K0354 K354: Follow proper procedures when the automatic sprinkler systems was out of service for more than 10 hours.
Short Summary

The facility did not implement a fire watch or post required signage when the sprinkler system was out of service, and staff including a CNA and the ADON were unaware of the outage, as revealed by inspection and interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙