K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
F

Failure to Perform and Document Required Emergency and Exit Lighting Tests

Adams County ManorWest Union, Ohio Survey Completed on 03-25-2026

Summary

The facility failed to perform and document required monthly and annual inspections of emergency and exit lighting in accordance with NFPA 101, 2012 Edition, sections 19.2.9.1 and 7.9.3.1.2, affecting all 69 residents in the building. During record review on 03/25/26 beginning at 8:45 A.M., surveyors found no documentation verifying that the battery back-up emergency lights located throughout the facility had been tested for the required 90-minute annual duration. Documentation of these tests was requested at the entrance conference at 8:40 A.M., and again at 9:35 A.M. and 10:10 A.M., but no records were provided by the time of exit. The Maintenance Director confirmed during interview that the requested documentation was not available, verifying the deficiency in required emergency lighting testing and recordkeeping. No specific residents, medical histories, or clinical conditions were described in the report beyond the statement that 69 residents were potentially affected.

Plan Of Correction

1.Based on record review and staff interview, no residents experienced negative outcomes related to failure to perform and document required emergency lighting testing. 2.The Medical Director was notified on 03/26/2026 by LNHA that the facility failed to provide documentation verifying battery back-up emergency lights were tested annually for 90 minutes as required. 3.Emergency lighting testing [for 90 minutes] will be completed by Maintenance Director/designee on or before 04/30/2026. Testing will be added to an annual automatically recurring schedule by Administrator/designee. 4.Documentation will be maintained and reviewed. Compliance will be reviewed in QAPI quarterly and as needed. 5. LNHA educated Maintenance Director on 03/26/2026 regarding the requirements for maintaining emergency lighting.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0291 citations
Failure to Document Required Annual 90‑Minute Emergency Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not have documentation showing completion of the required annual 90‑minute test of emergency lighting. During record review and interview, the Director of Facilities confirmed that records of this annual test, required under NFPA 101 sections 19.2.9.1 and 7.9, were not available. This deficiency was cited as affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Annual 90‑Minute Emergency Battery Lighting Test
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility did not perform and/or could not document the required annual 90‑minute test of battery-powered emergency lighting as required by NFPA 101 (2012 and 2021). During a record review with the Maintenance Director, no records were available to show that the annual 90‑minute emergency lighting test had been completed, and the Maintenance Director acknowledged the absence of this documentation, resulting in a cited deficiency affecting all occupants of the building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Required Emergency Battery Backup Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors found that the facility failed to maintain and document required testing of emergency battery backup lighting in accordance with NFPA 101. During record review with the Maintenance Director, no documentation was available for the monthly 30-second tests or the annual 90-minute tests for all sampled battery backup emergency lights. The Maintenance Director acknowledged the absence of these records, and the deficiency was determined to affect all residents and staff.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Emergency Lighting Testing
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not provide documentation to verify that required monthly and annual tests of battery-powered emergency lighting were performed, as confirmed by both document review and interviews with the DON and Director of Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Emergency Lighting Test
C
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

Surveyors determined that the facility did not conduct or document the required annual 90-minute test of battery backup emergency lighting. This was confirmed by facility leadership during the survey process.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Conduct Monthly Emergency Lighting Tests
F
K0291 K291: Install emergency lighting that can last at least 1 1/2 hours.
Short Summary

The facility did not perform or document required monthly emergency lighting tests for several months, as confirmed by record review and the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙