K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
F

Failure to Maintain and Document Required Generator Testing and Safety Features

Adams County ManorWest Union, Ohio Survey Completed on 03-25-2026

Summary

Surveyors identified a deficiency related to the testing and maintenance of the facility’s essential electrical system and generators. During record review, they found no documentation to verify that the facility’s three generators were tested monthly as required by NFPA 99 and NFPA 110. Additionally, there was no documentation provided to show that the three generators were inspected and tested annually as required by code. Documentation of these tests and inspections was requested at the entrance conference and again later in the morning, but no records were produced by the time of survey exit. During the physical tour of the facility, surveyors observed that none of the three generators had remote manual stop buttons. An interview with the Maintenance Director confirmed the absence of these remote manual stop buttons at the time of observation. These findings were determined to be out of compliance with NFPA 99 – 2012 Edition, Section 6.4.4 through 6.5.4.2 and NFPA 110 – 2010 Edition 5.6.5, and the deficient practice had the potential to affect all 69 residents in the facility.

Plan Of Correction

1.Based on record review, observation, and staff interview, no residents experienced negative outcomes related to the facility's failure to test and maintain the essential electrical system in accordance with NFPA requirements. Findings identified during the survey included: • The facility failed to provide documentation verifying that the three generators were tested monthly as required. • The facility failed to provide documentation verifying that the three generators were inspected and tested annually as required. • During observation on 03/25/2026, it was identified that the facility's three generators did not have remote manual stop buttons installed. 2.The Medical Director was notified by LNHA on 03/26/2026 of the deficiency, including failure to perform and document required generator testing, lack of annual inspection documentation, and absence of required remote manual stop devices. 3.Generator system inspection, testing, and maintenance will be completed by a contracted generator service provider and/or Maintenance Director/designee on or before 04/30/2026. Corrective actions will include: • Completion of monthly generator testing under load conditions, including verification of automatic transfer within 10 seconds. • Completion of annual generator inspection and testing, including full system evaluation in accordance with NFPA 110 requirements. • Installation of remote manual stop buttons for all three generators in accordance with code requirements. • Verification that all generator components, transfer switches, and associated equipment are functioning properly. • Establishment of a comprehensive generator testing and maintenance program, including weekly inspections, monthly load testing (20–40 day intervals), and required periodic extended testing. • All generator testing, inspection, and maintenance activities will be placed on an automatically recurring schedule by Administrator/designee on or before 04/30/2026. Documentation logs will be implemented and maintained onsite. 4.Documentation of all generator inspections, testing, and maintenance will be maintained onsite and readily available. The Maintenance Director/designee will conduct weekly and monthly audits to ensure compliance with NFPA 99 and NFPA 110 requirements. Compliance will be reviewed in QAPI every quarter and as needed to ensure ongoing systemic compliance 5.LNHA educated Maintenance Director on 03/26/2026 regarding the requirements for maintaining the facility's generators, including inspection and testing.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0918 citations
Failure to Perform and Document Annual Main and Feeder Breaker Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to perform and/or document required annual testing and exercising of main and feeder circuit breakers in accordance with NFPA 99 and manufacturer recommendations. During record review, no documentation could be produced to show that the annual breaker exercises had been completed, and the Director of Facilities acknowledged this lack of records. This deficiency relates to the essential electrical system that supports life safety and critical branches during emergencies.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Exercise and Document Main and Feeder Breaker Maintenance per NFPA 99
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility did not have documentation showing that the essential electrical system’s main and feeder circuit breakers were exercised annually in accordance with manufacturer recommendations and NFPA 99 requirements. During record review with the Maintenance Director, no records could be produced to verify that these breakers had been properly exercised, and the Maintenance Director acknowledged this failure. This deficiency was cited as affecting all occupants due to noncompliance with required essential electrical system maintenance and testing standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Required Generator Battery Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to perform and document required testing of backup generator batteries in accordance with NFPA 110. During record review, no documentation of generator battery testing was available, and the Maintenance Director acknowledged both the lack of records and a lack of knowledge of the NFPA 110 battery testing requirements. The report notes that this failure could result in loss of power affecting life support and life safety features for occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Required Generator Battery Testing Documentation
D
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors identified a deficiency when the facility could not provide documentation that backup generator batteries were being tested in accordance with NFPA 110 and NFPA 99 requirements. During record review, no records of generator battery testing were available, and the Maintenance Director confirmed he was unable to locate the requested documentation. This failure concerns the essential electrical system that supports life safety and critical functions during power loss.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Required Generator Battery Conductance Testing for Essential Electrical System
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors found that the facility failed to maintain its Essential Electrical System (EES) in accordance with NFPA 99 and related standards when record review showed that conductance testing was not performed for 2 of 2 sealed generator batteries over a defined period, and only one generator battery was tested during that time. During an interview, the Maintenance Director acknowledged that required testing had not been completed for both batteries. This lapse in required emergency power system maintenance affected the facility’s single EES and all residents and staff relying on it.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Essential Electrical System Testing
F
K0918 K918: Have generator or other power source capable of supplying service within 10 seconds.
Short Summary

Surveyors identified that the facility did not maintain required documentation for 1.5-hour load bank testing, monthly generator load testing, weekly voltage checks, or monthly conductance testing for generator batteries. These omissions were confirmed during a record review and acknowledged by facility leadership.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer