K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
F

Failure to Maintain Required Fire Alarm Documentation and Testing Records

Glades Health Care CenterPahokee, Florida Survey Completed on 04-29-2026

Summary

Surveyors identified deficiencies related to the facility’s fire alarm system testing and maintenance during record review with the Maintenance Director between 9:15 AM and 1:30 PM. The facility did not have a log book located at the fire alarm panel that was signed by the fire alarm vendor and documented the work completed at each visit, as required by NFPA 101 and NFPA 72. The Maintenance Director acknowledged that the facility failed to provide this log book at the fire panel. Additionally, the facility was unable to provide documentation that biennial smoke detector sensitivity testing had been performed, and the Maintenance Director confirmed that this documentation was not available. Surveyors also found that the fire alarm system design plans were not located at the fire panel as required. The Maintenance Director acknowledged that the facility failed to provide the fire alarm system design plans at the fire panel. These findings were cited under NFPA 101 2021 sections 9.6.5 and 9.6.7 and NFPA 72.

Plan Of Correction

The fire alarm book was placed at the fire panel with the pull station zones and building map. (Fire Alarm System Design Plan) This was completed on [R] The biennial sensitivity testing on the smoke detectors was completed on [R] The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation. The fire alarm book was placed at the fire panel with the pull station zones and building map. (Fire Alarm System Design Plan) This was completed on The biennial sensitivity testing on the smoke detectors was completed on The facility has determined that all residents have the potential to be affected. An in-service education program will be conducted by the administrator. The administrator will conduct for a period of three months a random audit of completed documentation,

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0345 citations
Failure to Perform and Document Annual Duct Detector Differential Testing
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to perform and/or document the required annual Duct Detector Differential testing for the fire alarm system in accordance with NFPA 101, NFPA 70, and NFPA 72. During record review and interviews with the Director of Facilities, no documentation could be produced to show that this annual testing had been completed, and the Director acknowledged the lack of records. This deficiency was cited as potentially affecting all occupants in the event of a fire or other emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Properly Test Fire Alarm System Components
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and properly test multiple fire alarm system components, including smoke detectors near the medical supply area and house laundry that could not be located, elevator fire hat and primary recall functions that could not be reset due to lack of a key, and an untested elevator control shunt trip. On revisit, the missing smoke detectors had been replaced with battery-operated units that were not connected to the building’s fire alarm notification system, and the previously identified fire alarm issues remained uncorrected.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Required Fire Alarm System Inspection and Testing Documentation
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

The facility did not maintain required inspection and testing documentation for its fire alarm system. During surveyor review, no records could be produced to show that semi-annual visual inspections or the two-year smoke detector sensitivity testing had been completed, and the maintenance supervisor confirmed that this documentation was unavailable at the time of the survey. This deficiency affected the entire facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Fire Alarm System in Proper Working Order
D
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors identified that the facility did not maintain its fire alarm system in accordance with NFPA 72 when the fire alarm control panel was observed displaying a trouble signal. During the observation, the Maintenance Director confirmed that the trouble condition was related to a faulty heat detector. This unresolved trouble indication showed that the fire alarm system was not being properly maintained to ensure it functioned as designed for the entire building.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform and Document Semi-Annual Fire Alarm System Inspections
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors determined that the facility did not comply with NFPA 101 and NFPA 72 requirements for fire alarm system maintenance when record review showed incomplete fire alarm inspection reports and no documentation of required semi-annual visual inspections of fire detection components. The Director of Maintenance confirmed that these six-month inspections had not been documented and reported being unaware of the requirement, creating a deficiency that had the potential to affect all four residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Document Fire Alarm System per NFPA Requirements
F
K0345 K345: Have approved installation, maintenance and testing program for fire alarm systems.
Short Summary

Surveyors found that the facility failed to maintain and document its fire alarm system in accordance with NFPA 101 and NFPA 72, potentially affecting all residents. The only annual fire alarm record provided was a single page without a device list, and there was no documentation of required semi-annual visual inspections or sensitivity testing of devices. During the tour, surveyors observed multiple fire alarm breakers in various electrical panels that were not marked in red, not secured from unauthorized access, and in one case left in the off position, with panel labeling insufficient to identify the presence of a fire alarm breaker. These findings were confirmed with the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙