K0341 K341: Install a fire alarm system that can be heard throughout the facility.
F

Deficient Installation of Fire Detection Devices

Alaris Health At BelgroveKearny, New Jersey Survey Completed on 12-05-2024

Summary

The facility failed to maintain smoke detectors and heat detectors in accordance with NFPA 101, NFPA 70, and NFPA 72 standards. During an observation, it was found that the smoke detector and heat detector in the elevator equipment room were not securely attached to their device bases and were hanging from the wires. This deficiency was identified during an observation on December 3rd, 2024, at 11:45 AM. The issue had the potential to affect 120 residents. During an interview at the time of the observation, the responsible individual was not aware of the deficient installation.

Plan Of Correction

The smoke detector and heat detector devices were secured to the device base in the elevator equipment room. All residents have the potential to be affected. The Maintenance Director audited all smoke and heat detector devices in the building to assure they were secured to the device base. No additional issues were identified. The Maintenance Director will make monthly rounds to ensure all smoke and heat detector devices are properly secured to the device base. The Maintenance Director will report the results of these audits to the Administrator on a monthly basis. The Maintenance Director will review the findings of the monthly audits at the Quarterly QAPI Meeting for the next 2 quarters.

Penalty

Fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0341 citations
Fire Alarm System Altered Without Required Plan Approval or Inspection
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility installed carbon monoxide detectors on its fire alarm system and placed the system into service without obtaining prior plan approval or completing an occupancy inspection, as confirmed by interviews with the DON and Director of Maintenance. No documentation of approval or completion was provided.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Smoke Detector Protection in Open Dining Room
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The 1st floor Dining Room had its doors removed, leaving the room open to the corridor without any smoke detector protection. This was confirmed by the Director of Facilities, resulting in a failure to provide required fire alarm protection in that smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Obstruction of Fire Alarm System Components
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

Surveyors observed that a smoke detector head was not properly mounted to the ceiling at the North Smoke Doors exit into the administration hall, and another smoke detector head in the North Mechanical closet was covered with a plastic bag. These issues were confirmed by the Facility Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Smoke Detector Placement Near Airflow Source
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

A smoke detector was found installed within three feet of direct airflow from an air return or supply near an exit door, contrary to NFPA 70 and NFPA 72 requirements. This installation issue was confirmed by Facility Maintenance and could impact 30 occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation of Fire Alarm Initiating Devices
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility did not properly install fire alarm initiating devices, affecting one level of the building. The manual pull station for the double exit doors in the Kitchen on the first floor was not mounted within 5 feet of the exit doors, as observed and confirmed during an interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙