K0341 K341: Install a fire alarm system that can be heard throughout the facility.
E

Fire Alarm System Altered Without Required Plan Approval or Inspection

Kadima Rehabilitation & Nursing At LititzLititz, Pennsylvania Survey Completed on 07-01-2025

Summary

The facility failed to obtain required plan approval and conduct an occupancy survey before making changes to its fire alarm system. Specifically, carbon monoxide detectors were installed on the existing fire alarm system without prior plan review or approval from the Department of Health. No documentation was provided to show that the necessary approvals were sought or granted before these modifications were made. Additionally, the facility placed the altered fire alarm system into service without completing an occupancy inspection or providing a record of completion for the changes. Interviews with the Director of Nursing and Director of Maintenance confirmed that the fire alarm system was altered and put into use without the required approval from the Pennsylvania Department of Health.

Plan Of Correction

K 0341 1. The facility cannot retroactively correct. 2. All new plans related to the fire alarm system will undergo both a formal plan review and an occupancy survey prior to implementation. 3. The Environmental Services Director has been re-educated on the requirements of regulation K0341. 4. The Nursing Home Administrator (NHA) or their designee will review all proposed changes to the fire alarm system to ensure full compliance with applicable codes and regulations.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0341 citations
Lack of Smoke Detector Protection in Open Dining Room
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The 1st floor Dining Room had its doors removed, leaving the room open to the corridor without any smoke detector protection. This was confirmed by the Director of Facilities, resulting in a failure to provide required fire alarm protection in that smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Obstruction of Fire Alarm System Components
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

Surveyors observed that a smoke detector head was not properly mounted to the ceiling at the North Smoke Doors exit into the administration hall, and another smoke detector head in the North Mechanical closet was covered with a plastic bag. These issues were confirmed by the Facility Maintenance Director during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Smoke Detector Placement Near Airflow Source
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

A smoke detector was found installed within three feet of direct airflow from an air return or supply near an exit door, contrary to NFPA 70 and NFPA 72 requirements. This installation issue was confirmed by Facility Maintenance and could impact 30 occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation of Fire Alarm Initiating Devices
E
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility did not properly install fire alarm initiating devices, affecting one level of the building. The manual pull station for the double exit doors in the Kitchen on the first floor was not mounted within 5 feet of the exit doors, as observed and confirmed during an interview with the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Installation of Fire Detection Devices
F
K0341 K341: Install a fire alarm system that can be heard throughout the facility.
Short Summary

The facility failed to maintain smoke and heat detectors according to NFPA standards, as observed in the elevator equipment room where the devices were hanging from wires and not securely attached. This issue had the potential to affect 120 residents, and the responsible individual was unaware of the deficiency.

Fine: $25,635
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙