K0511 K511: Have properly installed electrical wiring and gas equipment.
E

Failure to Maintain Electrical Wiring in Compliance with NFPA 70

Chapel ManorPhiladelphia, Pennsylvania Survey Completed on 12-23-2024

Summary

The facility failed to maintain and protect electrical wiring in accordance with NFPA 70, the National Electric Code. During an observation on December 23, 2024, at 10:40 a.m., it was noted that in the Basement's Elevator Machine Room, the covers were not mounted on the elevator control panels. This deficiency was confirmed during an exit interview with the Assistant Administrator and the Maintenance Director at 11:00 a.m. on the same day.

Plan Of Correction

Electrical wiring in the elevator room has been repaired. Maintenance Dir/designee will re-educate maintenance staff on maintaining wiring are not exposed. Maintenance dir/designee will complete initial audit to ensure electrical wires are not exposed. NHA/designee will complete weekly audits x3 and monthly x 1 to ensure compliance. Maintenance Director will report the findings of the audits to the QAPI Committee X 3 months.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-GFCI Electrical Outlet Near Sink in Medication Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed that an electrical outlet in Nursing Station 1's med room was installed 18 inches from a sink and was not equipped with a required ground-fault circuit interrupter (GFCI), as mandated by NFPA 70, National Electrical Code. The DES confirmed during the survey that this outlet lacked GFCI protection, resulting in a cited deficiency related to utilities and electrical safety in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙