K0511 K511: Have properly installed electrical wiring and gas equipment.
D

Non-GFCI Electrical Outlet Near Sink in Medication Room

Claremont Manor Care CenterClaremont, California Survey Completed on 03-12-2026

Summary

Surveyors found that the facility failed to ensure electrical safety in accordance with NFPA 70, National Electrical Code, 2011 Edition, Section 210.8. During an observation in Nursing Station 1's medication room, an electrical outlet was identified 18 inches from a sink that was not equipped with the required ground-fault circuit interrupter (GFCI). The Director of Environmental Services (DES) was present during the observation and confirmed that the outlet, located near the sink, did not have a GFCI. This deficiency affected one of four smoke compartments and was cited as noncompliance with NFPA 101 requirements for utilities, gas, and electric systems. No specific residents or their medical conditions were mentioned in relation to this deficiency, and the report focused solely on the physical environment and the noncompliant electrical installation near the sink in the medication room.

Plan Of Correction

K511 - Utilities - Gas and Electric (NFPA 70) How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice. There were no residents identified as directly affected by this deficient practice. Upon identification on 3/12/2026, the facility immediately removed the outlet from use and implemented interim safety measures. A licensed electrician was contacted to install a GFCI-protected outlet at Nursing Station 1 medication room sink area. The GFCI outlet was installed on 3/12/2026 to ensure compliance with NFPA 70 requirements and reduce risk of electrical shock. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken. On 3/12/2026, the Director of Environmental Services (DES) conducted a facility-wide audit of all electrical outlets located within proximity to water sources, including medication rooms, kitchen areas, and resident care areas. Any outlets identified as not GFCI-protected were immediately removed from service and scheduled for correction by a licensed electrician. What measures will be put into place or what systemic changes will the facility make to ensure that the deficient practice does not recur. To prevent recurrence, the facility has implemented a preventive maintenance program that includes routine inspection of all electrical outlets near water sources for GFCI compliance. On 3/13/2026, the DES re-educated staff on NFPA 70 requirements, specifically related to GFCI installation near sinks and wet locations. The facility will ensure that all future electrical work is reviewed for compliance with applicable codes and completed by licensed professionals. How the facility plans to monitor its performance to make sure that solutions are sustained. The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The DES or designee will conduct weekly environmental rounds for 3 months to ensure all outlets near water sources are GFCI-protected and functioning properly. Findings will be reported to the Administrator and included in the quarterly QAPI meeting. Any deficiencies will be corrected immediately. The QAPI committee will monitor compliance until sustained. Include dates when corrective actions will be completed. The corrective action completion dates must be acceptable to the State Agency. 4/1/2026

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficient Maintenance of Sprinkler Systems and Improper Storage in Electrical Panel Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that sprinkler deflectors in several rooms had accumulations of dust and mildew, and the electrical panel room was being used for storage and as an office, with items placed too close to the electrical panel. The maintenance supervisor acknowledged these deficiencies, which were not in compliance with facility policy and relevant safety codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙