K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
E

Non-compliance with Self-Closing Door Requirements

Sayre Health Care CenterSayre, Pennsylvania Survey Completed on 03-19-2025

Summary

The facility failed to maintain compliance with NFPA 101 standards regarding doors with self-closing devices. During an observation on March 19, 2025, at 10:48 a.m., it was noted that the door to the Dietary Dry storage area was being held open by an unapproved means, specifically a rubber wedge. This deficiency affected one of the eight smoke compartments within the facility. The issue was confirmed during an exit interview with the Facility Administrator and Facility Maintenance on the same day at 11:45 a.m.

Plan Of Correction

The Maintenance Director promptly took out the rubber wedge and closed the door to the dry food storage room. The facility Administrator educated both the Maintenance Director and the Food Service Director that, in accordance with life safety regulations, this door must never be propped open. To ensure compliance, the Maintenance Director will conduct weekly audits for a duration of four weeks, followed by monthly audits for three months, to verify that the dry food storage room door remains closed. The findings from these audits will be presented at the monthly Quality Assurance meeting for evaluation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0223 citations
Fire-Rated Door in Hazardous Area Improperly Propped Open
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

Surveyors found that a fire-rated door leading to a hazardous dry storage room, protected by a one-hour fire barrier and equipped with a self-closing device, was held open by a bungee cord and obstructed by a storage rack, preventing it from self-closing and latching as required by NFPA 101. The Administrator confirmed the door should remain closed, and the deficiency was cited based on these observations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Doors in Hazardous Area
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

Surveyors observed that the clean linen closet doors near room 216 were left open and did not close to a positive latch when tested, as confirmed by maintenance staff. These doors are required to be self-closing and kept closed unless held open by an approved device, and the failure to do so resulted in a deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Door Latching Mechanism
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

A corridor kitchen door equipped with a self-closing device was found not to latch when tested during a facility tour, as confirmed by the Maintenance Director. This deficiency impacted 32 residents in one smoke compartment and resulted in noncompliance with NFPA 101 standards for self-closing doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Doors
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility failed to maintain two doors with self-closing devices, affecting one smoke compartment. Observations revealed that the doors at Nurse's Station 2 and Resident Room 62 did not positively latch into their frames. This issue was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with NFPA 101: Self-Closing Door Devices
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility was found non-compliant with NFPA 101 standards as eight doors with self-closing devices were either missing door closers or held open with magnets not connected to the fire alarm system. These issues were identified during a fire safety tour and acknowledged by the Plant Operations Technician.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Closure Arm on Basement Library Door
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility did not comply with NFPA 101 requirements for self-closing doors, as observed in the basement library where a door was missing a closure arm. This was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.