K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
E

Failure to Maintain Self-Closing Doors in Hazardous Area

Heartwood Lodge Trinity HealthSpring Lake, Michigan Survey Completed on 06-10-2025

Summary

During an observation on June 10, 2025, at approximately 10:06 AM, surveyors found that the doors to the clean linen closet located in the 200 hall near room 216 were open and did not close to a positive latch when tested. This was confirmed through interviews with two facility maintenance staff present at the time. The doors in question are required to be self-closing and kept in the closed position unless held open by an approved release device, in accordance with regulatory standards. The failure to ensure these doors were properly self-closing and latched constituted a deficiency, as it did not comply with the requirements for doors in exit passageways, stairway enclosures, horizontal exits, smoke barriers, or hazardous area enclosures.

Plan Of Correction

Element 1 - Upon identification, environmental services staff repaired the latch to the clean linen closet located at the 200 hall near room 216. This latch now closes "per positive latch" as required. Element 2 - Environmental Services Director Designee inspected all other clean linen closet doors to assure compliance. Element 3 - The Environmental Services Director/designee will complete monthly audits for 3 months of auto latching doors to ensure compliance in accordance with NFPA 101 7.2.1.8.2. Element 4 - The Environmental Services Director/designee will report audit findings to the Quality Assurance / Performance Improvement (QAPI) Committee quarterly x 3 with further monitoring per QAPI recommendations. Any identified issues will trigger retraining and/or corrective action. Element 5 - The Nursing Home Administrator is responsible for maintaining compliance.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0223 citations
Fire-Rated Door in Hazardous Area Improperly Propped Open
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

Surveyors found that a fire-rated door leading to a hazardous dry storage room, protected by a one-hour fire barrier and equipped with a self-closing device, was held open by a bungee cord and obstructed by a storage rack, preventing it from self-closing and latching as required by NFPA 101. The Administrator confirmed the door should remain closed, and the deficiency was cited based on these observations.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Door Latching Mechanism
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

A corridor kitchen door equipped with a self-closing device was found not to latch when tested during a facility tour, as confirmed by the Maintenance Director. This deficiency impacted 32 residents in one smoke compartment and resulted in noncompliance with NFPA 101 standards for self-closing doors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Self-Closing Doors
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility failed to maintain two doors with self-closing devices, affecting one smoke compartment. Observations revealed that the doors at Nurse's Station 2 and Resident Room 62 did not positively latch into their frames. This issue was confirmed during an exit interview with the Facility Administrator and Facilities Manager.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with NFPA 101: Self-Closing Door Devices
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility was found non-compliant with NFPA 101 standards as eight doors with self-closing devices were either missing door closers or held open with magnets not connected to the fire alarm system. These issues were identified during a fire safety tour and acknowledged by the Plant Operations Technician.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-compliance with Self-Closing Door Requirements
E
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility was found non-compliant with NFPA 101 standards as a door in the Dietary Dry storage area was held open by a rubber wedge, affecting one of eight smoke compartments. This was confirmed during an exit interview with the Facility Administrator and Maintenance.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Closure Arm on Basement Library Door
D
K0223 K223: Provide exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Short Summary

The facility did not comply with NFPA 101 requirements for self-closing doors, as observed in the basement library where a door was missing a closure arm. This was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙