K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
D

Failure to Maintain Required Fire Extinguishers in TER

Miami Shores Nursing And Rehab CenterMiami, Florida Survey Completed on 04-01-2025

Summary

The facility was found to be non-compliant with NFPA 101 standards regarding the maintenance of portable fire extinguishers. During a life safety tour conducted at 2:40 p.m. on April 1, 2025, it was observed that the Telecommunication Equipment Room (TER) in the Rehabilitation Room lacked the required clean agent fire extinguishers. This deficiency was identified during an inspection with the Maintenance Director present. The Maintenance Director acknowledged the absence of the necessary fire extinguishers during a staff interview conducted at the same time. This issue was further discussed and acknowledged by the facility's Administrator during the exit conference. The deficiency was noted under NFPA 101 (2021 Edition) and NFPA 10 (2018 Edition) standards, indicating a failure to adhere to the required fire safety protocols.

Plan Of Correction

Sprinkler System Maintenance and Testing Identify patients that were at risk and what did: When the surveyor identified the issue we contacted vendor and ordered a new Clean Agent Fire Extinguisher to be added to the Telecommunication room. This was installed on 4/17/2025. How will you identify other patients that are at risk? No other residents were identified at risk. When the surveyor identified the issue, we contacted vendor and ordered a new Clean Agent Fire Extinguisher to be added to the Telecommunication room. This was installed on 4/17/2025. Measure put in place: The Director of Plant Operations has added the new extinguishers to his monthly checks for compliance. The Director also checked the rest of the extinguishers to ensure they were ready for use. How will you monitor? The Director of Plant Operations has added the new extinguishers to his monthly checks for compliance. Any variances will be brought to the QAPI Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Accessibility of Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

Surveyors found that 12 out of 18 portable fire extinguishers were installed with the top of the handle positioned above the sixty-inch maximum height allowed by NFPA 101 and NFPA 10, with some as high as sixty-three inches. In one case, a trash can obstructed access to a fire extinguisher cabinet. The Maintenance Director acknowledged these findings during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙