K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
F

Improper Installation and Accessibility of Portable Fire Extinguishers

Royal Palm Beach Health And Rehabilitation CenterRoyal Palm Beach, Florida Survey Completed on 05-27-2025

Summary

Surveyors observed that the facility failed to install and maintain portable fire extinguishers in accordance with NFPA 101 and NFPA 10 standards. Specifically, 12 out of 18 sampled fire extinguishers were found to be mounted in cabinets with the top of the handle positioned more than sixty inches above the finished floor, with measurements ranging from sixty and a half inches to sixty-three inches. This was noted in multiple locations throughout the facility, including the kitchen, various corridors, near the nurses' station, the rehabilitation suite, and near the maintenance office. In one instance, a trash can was placed in front of a fire extinguisher cabinet, initially obstructing the cabinet door from opening until it was moved. The observations were made during a fire safety tour conducted with the Maintenance Director, who acknowledged the findings at the time. The issue was also reviewed with the Administrator, the Regional Maintenance Director, and the Maintenance Director during the exit conference. The report does not mention any specific residents or staff being directly affected at the time of the deficiency, nor does it provide details about any medical history or conditions related to the deficiency. Additionally, the report notes that the facility failed to maintain smoking areas in accordance with NFPA 101 for both of its designated smoking areas. However, the detailed findings and observations in the report focus primarily on the improper installation height and accessibility of portable fire extinguishers, as well as the temporary obstruction of access to one extinguisher by a trash can.

Plan Of Correction

Corrective Actions On 6/9/2025, the following locations' fire extinguishers were replaced with a shorter extinguisher so that the top of the new extinguisher is less than 60 inches from the floor: A. Kitchen. Two extinguishers. B. East Corridor. Near the Staff Development Office. C. East Corridor. Near the kitchen entrance. D. SE Corridor. Near room 100. E. South Corridor. Near room 100. F. SW Corridor. Near the Nurses Station. G. West Corridor. Near room 126. H. West Corridor. Near the Maintenance Office. I. Rehabilitation Suite. J. North Corridor. Near the exit. K. North Corridor. Near room 213. L. North Corridor. Near room 200. Identification of Others Potentially Affected All fire extinguishers in cabinets were accounted for, so no further evaluation was needed. Systemic Changes The Maintenance Director, or designee, will perform documented monthly inspections for three months of the facility fire extinguishers placed in cabinets to ensure the top of the extinguisher is less than 60 inches from the floor. Quality Assurance Results of the monthly inspections will be presented at the monthly QA meetings for three months. If substantial compliance is not met after three months, results of the ongoing monthly inspections will be brought to QA meetings until substantial compliance is met. K 355 Immediate Corrective Action 1. The Courtyard was cleaned of cigarette butts on the ground on 5/28/2025. 2. The designated smoking area near the

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Fire Extinguisher Mounted Above Allowed Height
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A fire extinguisher in the laundry room was found mounted at 66 inches above the floor, exceeding the height limit set by NFPA 10. This noncompliance was confirmed by the Maintenance Director and could affect about six occupants during a fire emergency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙