K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
C

Lack of Documentation for Electrical Receptacle Inspections

River's Bend Health & Rehab CenterHarrisburg, Pennsylvania Survey Completed on 03-13-2025

Summary

The facility failed to provide documentation verifying that electrical receptacles in Patient Care Areas had been subjected to inspection and testing. This deficiency was identified during a document review conducted on March 13, 2025, between 8:45 AM and 10:45 AM. The review revealed a lack of documentation confirming that the required testing and inspection of electrical receptacles had been performed. During an exit conference on the same day at 1:45 PM, the Administrator and Maintenance Director confirmed the absence of such documentation, affecting the entire component of the facility's electrical systems in Patient Care Areas.

Plan Of Correction

The electrical receptacles in Patient Care Areas have been inspected. All facility receptacles will be inspected. The Maintenance Director has been re-educated on the requirement to inspect all electrical receptacles in Patient Care Areas. The NHA or designee will audit the inspection results semiannually for proper documentation and placement in the Life Safety Book.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0914 citations
Failure to Perform and Document Required Annual Receptacle Testing
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors found that the facility did not perform or could not document required annual testing of electrical receptacles for tension and polarity in patient care areas, as mandated by NFPA 99. During record review with the Maintenance Director, no evidence was produced to show that hospital‑grade and other required receptacles had been tested at the specified intervals, and the Maintenance Director acknowledged this lack of documentation. This noncompliance with NFPA 99 Section 6.3.4 was cited as a deficiency affecting all occupants who rely on the facility’s electrical systems.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Required Polarity Testing of Electrical Receptacles
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors identified that the facility did not fully comply with NFPA 99 requirements for electrical receptacle maintenance and testing. Review of the electrical receptacle testing log showed that only tension testing was documented, with no evidence of polarity testing being conducted. During interview, the Maintenance Director confirmed that staff had never tested receptacle polarity. This deficiency was cited as affecting the entire facility and was noted as potentially causing faulty electrical equipment which can result in fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not provide documentation verifying that annual inspections and testing of electrical receptacles in resident care areas were completed, as required by NFPA 99. This deficiency was confirmed by both the Administrator and the Director of Maintenance, and affected all smoke zones within the component.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test Electrical Receptacles at Resident Bed Locations
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not perform required testing of electrical receptacles at resident bed locations, including both hospital-grade and non-hospital grade outlets, as mandated by regulations. Documentation and interviews confirmed that testing for physical integrity, polarity, and grounding blade retention force was not conducted throughout the facility.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test and Repair Hospital-Grade Electrical Receptacles
E
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Multiple hospital-grade electrical outlets in resident rooms failed inspection, and there was no documentation showing that these outlets were repaired or replaced as required. This deficiency was confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical System Testing and Installation
D
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to accurately test electrical receptacles in resident care areas and lacked documented performance data. Additionally, improper installation of a power cord passing through the ceiling into interstitial space was observed, with a power strip used as permanent wiring above the fire sprinkler system, posing a potential fire hazard. These issues were confirmed by the Director of Maintenance and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙