K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
F

Failure to Test Electrical Receptacles at Resident Bed Locations

Lutheran Community At TelfordTelford, Pennsylvania Survey Completed on 07-08-2025

Summary

The facility failed to ensure that electrical receptacles at resident bed locations were tested according to required intervals. Specifically, document review revealed that non-hospital grade receptacles were not tested at intervals not exceeding 12 months, and hospital-grade receptacles were not tested based on documented performance data, with a minimum frequency of at least every 12 months. The required testing includes visual inspection of physical integrity, verification of correct polarity of hot and neutral connections, and measurement of the retention force of the grounding blade, except for locking-type receptacles. These requirements apply to all resident care rooms throughout the facility. During the survey, the Maintenance Director confirmed in an exit interview that testing of electrical receptacles at resident bed locations had not been performed. The deficiency affects the entire facility, as the lack of testing was not limited to a specific area or group of residents. No information was provided regarding specific residents or their medical conditions in relation to this deficiency.

Plan Of Correction

Electrical receptacle testing documentation not provided at survey was obtained. Electrical receptacle testing of hospital and non-hospital grade receptacles was completed in November 2024. Hospital and non-hospital grade receptacles testing will occur again in November 2025 so as not to exceed the 12-month requirement. Inspection will be entered in the electronic preventative maintenance program as a task to be completed as required. Monitored by Director of Maintenance or designee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0914 citations
Failure to Perform and Document Required Annual Receptacle Testing
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors found that the facility did not perform or could not document required annual testing of electrical receptacles for tension and polarity in patient care areas, as mandated by NFPA 99. During record review with the Maintenance Director, no evidence was produced to show that hospital‑grade and other required receptacles had been tested at the specified intervals, and the Maintenance Director acknowledged this lack of documentation. This noncompliance with NFPA 99 Section 6.3.4 was cited as a deficiency affecting all occupants who rely on the facility’s electrical systems.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Perform Required Polarity Testing of Electrical Receptacles
F
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Surveyors identified that the facility did not fully comply with NFPA 99 requirements for electrical receptacle maintenance and testing. Review of the electrical receptacle testing log showed that only tension testing was documented, with no evidence of polarity testing being conducted. During interview, the Maintenance Director confirmed that staff had never tested receptacle polarity. This deficiency was cited as affecting the entire facility and was noted as potentially causing faulty electrical equipment which can result in fire.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Annual Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility did not provide documentation verifying that annual inspections and testing of electrical receptacles in resident care areas were completed, as required by NFPA 99. This deficiency was confirmed by both the Administrator and the Director of Maintenance, and affected all smoke zones within the component.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Test and Repair Hospital-Grade Electrical Receptacles
E
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

Multiple hospital-grade electrical outlets in resident rooms failed inspection, and there was no documentation showing that these outlets were repaired or replaced as required. This deficiency was confirmed by the Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical System Testing and Installation
D
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to accurately test electrical receptacles in resident care areas and lacked documented performance data. Additionally, improper installation of a power cord passing through the ceiling into interstitial space was observed, with a power strip used as permanent wiring above the fire sprinkler system, posing a potential fire hazard. These issues were confirmed by the Director of Maintenance and acknowledged by the Administrator.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of Documentation for Electrical Receptacle Inspections
C
K0914 K914: Ensure receptacles at patient bed locations and where general anesthesia is administered, are tested after initial installation, replacement or servicing.
Short Summary

The facility failed to document the inspection and testing of electrical receptacles in Patient Care Areas. A review revealed missing documentation verifying that these inspections had been conducted, which was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙