K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
F

Deficiencies in Fire/Smoke Barrier Construction

Palm Garden Of Vero BeachVero Beach, Florida Survey Completed on 04-30-2025

Summary

The facility failed to maintain their fire/smoke barrier construction in accordance with NFPA 101 standards. During a fire safety tour conducted on April 30, 2025, several deficiencies were observed in the smoke barriers of the facility. Specifically, the Reflection Wing's 1-hour smoke wall near Room 106 had five penetrations above the ceiling, and near Room 104, there were three penetrations. Additionally, the Seaway Wing's 2-hour fire-rated wall near Room 206 had four penetrations above the ceiling. These penetrations in the smoke barriers compromise the integrity of the fire resistance rating, which is crucial for restricting the movement of fire and smoke in the event of an emergency. The Plant Operations Technician acknowledged these findings during the inspection, and the issues were communicated to the Administrator and the Director of Plant Operations during the exit conference. The report emphasizes that these examples are not exhaustive, and a thorough inspection of each barrier should be conducted to ensure all penetrations are identified and properly sealed. The penetrations in fire-rated barriers must be sealed with a UL-listed approved system to restore the original fire or smoke-rated integrity of the walls, ceilings, and floors.

Plan Of Correction

No residents were affected by this alleged deficient practice as of 05/16/2025 and none can be identified as of 05/16/2025. The maintenance director and assistants were educated by the Executive Director on 05/16/2025 on K372. The center smoke walls were inspected above the ceilings throughout the center on 05/16/2025 to identify any other penetrations needing to be sealed by the maintenance director/designee. 1. The Reflection Wing 1-hour smoke wall, near Room 106, had the five penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. 2. The Reflection Wing 1-hour smoke wall, near Room 104, had the three penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. 3. The Seaway Wing 2-hour fire rated wall, near Room 206, had the four penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. Fire penetrations above the ceiling will be audited for compliance with K372 by the maintenance director/designee weekly x4 weeks, monthly x6 months and the results of these audits will be brought to QAPI for review. No residents were affected by this alleged deficient practice as of 05/16/2025 and none can be identified as of 05/16/2025. The maintenance director and assistants were educated by the Executive Director on 05/16/2025 on K372. The center smoke walls were inspected above the ceilings throughout the center on 05/16/2025 to identify any other penetrations needing to be sealed by the maintenance director/designee. 1. The Reflection Wing 1-hour smoke wall, near Room 106, had the five penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. 2. The Reflection Wing 1-hour smoke wall, near Room 104, had the three penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. 3. The Seaway Wing 2-hour fire rated wall, near Room 206, had the four penetrations above the ceiling repaired on 05/20/25 by the maintenance director/designee. Fire penetrations above the ceiling will be audited for compliance with K372 by the maintenance director/designee weekly x4 weeks, monthly x6 months and the results of these audits will be brought to QAPI for review.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0372 citations
Improper Repair of Smoke Barrier Penetrations in Multiple Smoke Compartments
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire-rated enclosures were not properly maintained, with penetrations in smoke barriers in several general storage rooms across multiple smoke compartments. The Maintenance Director stated that insulation and fiberglass were used to pack and cover these holes but could not confirm that the materials were approved for fire-rated construction. Inspectors observed penetrations covered with fiberglass and noted a hole in one fiberglass panel in a storage room, resulting in a deficiency under NFPA 101 requirements for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetrations in Smoke/Fire Barriers After Electrical Work
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that smoke/fire barriers in three of fourteen smoke compartments, including the hot water room, the barrier between the kitchen and a smoke compartment, and the smoke wall leading to the Alzheimer’s unit, had penetrations that were not properly fire-stopped. During the on-site interview, the Maintenance Director acknowledged that recent electrical work had been completed and that the contractor failed to seal these penetrations, resulting in noncompliance with NFPA 101 smoke barrier construction requirements.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

A deficiency was identified when an unsealed penetration around data wires was observed in a smoke barrier wall on the second floor near the Rehabilitation Department. This issue was confirmed by the Administrator and Maintenance Director and affected one of two floors.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unprotected Penetration in Smoke Barrier Wall
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

An unprotected penetration was found in a smoke barrier wall above double doors near the ADON/Medical Records Office, where blue and red wires passed through without proper protection. This issue, confirmed by the Director of Maintenance, affected two of twelve smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unsealed Wire Penetrations in Smoke Barrier
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found that two wires passed unsealed through a smoke barrier above the ceiling near a resident corridor, with the Maintenance Director confirming unawareness of the sealing requirement. This deficiency had the potential to affect five residents and did not comply with NFPA 101-2012 standards for smoke barrier construction.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain Smoke Barrier Integrity per NFPA 101
E
K0372 K372: Ensure smoke barriers are constructed to a 1 hour fire resistance rating.
Short Summary

Surveyors found multiple penetrations in smoke barriers sealed with non-fire-rated materials and one unsealed pipe, compromising the required fire and smoke resistance in several corridors and the attic. Maintenance leadership confirmed uncertainty about the materials used, and these deficiencies had the potential to affect all 39 residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙