K0912 K912: Have power receptacles that are properly grounded.
E

Non-Compliance with GFI Protection Near Water Sources

Chambersburg Skilled Nursing And Rehabilitation CeChambersburg, Pennsylvania Survey Completed on 04-16-2025

Summary

The facility failed to maintain power receptacles with Ground Fault Interruption (GFI) protection within six feet of a water source in three of six smoke zones. During an observation on April 16, 2025, between 12:30 PM and 12:45 PM, it was noted that various outlets were not GFI protected. Specifically, at 12:30 PM, one outlet in the D Hall Nurses' Station Nourishment Area was found to be non-compliant. At 12:40 PM, three outlets in the B Hall Beauty Shop, located by sinks, were also not GFI protected. Additionally, at 12:45 PM, two outlets in the Main Kitchen Prep Area, near the coffee machine and ice machine, were identified as lacking GFI protection. This was confirmed during an interview with the Assistant Director of Nursing and the Maintenance Director at the time of the exit conference on the same day.

Plan Of Correction

1 and 2. Maintenance Director has updated GFI's in D hall nurses station nourishment room (1 outlet), B hall beauty shop (3 outlets), and main kitchen prep area (2 outlets). 3. Maintenance department will be educated on the standards of maintaining power receptacles to be GFI within six feet of a water source. 4. Maintenance or facility designee will audit facilities GFI receptacles weekly x2 for 2 months then quarterly throughout the year and results of the audit will be reported to the QA Committee.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0912 citations
Failure to Maintain GFCI Protection for Electrical Receptacles
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors identified that three electrical receptacles in the facility were not GFCI protected as required, including those near a sink in the café, a water fountain near the nurse station, and a juice machine in the kitchen. These deficiencies were confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Lack of GFCI Protection on Kitchen Electrical Receptacle
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

A kitchen electrical receptacle near the hand sink was found without required GFCI protection during an observation, and this deficiency was confirmed by the administrator and maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical Outlet Safety and Maintenance
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors found that an electrical outlet near a waterline was not GFI-protected, a damaged outlet faceplate was present in a resident room, and GFI outlets were not tested according to manufacturer instructions. Staff were unaware of these issues, and the deficiencies affected multiple residents and smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Receptacle Deficiency in Laundry Room
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility failed to maintain electrical receptacles in compliance with safety standards in one of over thirty rooms. An observation revealed that the A wing resident laundry room had a washing machine without GFCI protection. This deficiency was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain GFI Protection Near Water Sources
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not ensure that power receptacles were GFI protected within six feet of a water source in one of the smoke zones. Observations revealed non-GFI protected outlets behind an ice machine near a resident room and in the Boiler/Generator Room. This was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Electrical Receptacle Maintenance
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not maintain electrical receptacles according to NFPA 101 standards, lacking GFCI protection in the employee lounge water cooler and resident laundry washing machine. This was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙