K0912 K912: Have power receptacles that are properly grounded.
B

Lack of GFCI Protection on Kitchen Electrical Receptacle

Concordia Lutheran Health And Human CareCabot, Pennsylvania Survey Completed on 07-30-2025

Summary

During an observation conducted on July 30, 2025, at 11:36 a.m., it was found that an electrical receptacle located in the kitchen near the hand sink did not have ground fault circuit interrupter (GFCI) protection as required. This deficiency was confirmed through interviews with both the administrator and the maintenance supervisor at the same time. The report specifically notes that this issue was present in one of over twenty rooms observed. No additional details regarding patient involvement, medical history, or the condition of any residents at the time of the deficiency are provided in the report.

Plan Of Correction

Education will be provided to maintenance. All outlets within 6 feet of a water source are GFCI. The outlet by the hand sink was replaced to be GFCI on 7/30/25. The dietary manager or designee will audit the outlet by the hand sink to ensure it is GFCI weekly for 4 weeks. The results of these audits will be reviewed quarterly by the Quality Assurance and Quality Improvement committee for further analysis and recommendation.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0912 citations
Failure to Maintain GFCI Protection for Electrical Receptacles
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors identified that three electrical receptacles in the facility were not GFCI protected as required, including those near a sink in the café, a water fountain near the nurse station, and a juice machine in the kitchen. These deficiencies were confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiencies in Electrical Outlet Safety and Maintenance
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

Surveyors found that an electrical outlet near a waterline was not GFI-protected, a damaged outlet faceplate was present in a resident room, and GFI outlets were not tested according to manufacturer instructions. Staff were unaware of these issues, and the deficiencies affected multiple residents and smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-Compliance with GFI Protection Near Water Sources
E
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility was found non-compliant with GFI protection requirements for power receptacles within six feet of a water source in three smoke zones. Observations revealed non-GFI protected outlets in the D Hall Nurses' Station Nourishment Area, B Hall Beauty Shop, and Main Kitchen Prep Area. This was confirmed by the Assistant DON and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Electrical Receptacle Deficiency in Laundry Room
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility failed to maintain electrical receptacles in compliance with safety standards in one of over thirty rooms. An observation revealed that the A wing resident laundry room had a washing machine without GFCI protection. This deficiency was confirmed by the maintenance supervisor.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain GFI Protection Near Water Sources
D
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not ensure that power receptacles were GFI protected within six feet of a water source in one of the smoke zones. Observations revealed non-GFI protected outlets behind an ice machine near a resident room and in the Boiler/Generator Room. This was confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Deficiency in Electrical Receptacle Maintenance
B
K0912 K912: Have power receptacles that are properly grounded.
Short Summary

The facility did not maintain electrical receptacles according to NFPA 101 standards, lacking GFCI protection in the employee lounge water cooler and resident laundry washing machine. This was confirmed by the maintenance director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer