K0920 K920: Ensure proper usage of power strips and extension cords.
D

Improper Use of Power Strips for Refrigerators and Resident Equipment

Briarcliff Manor Center For Rehab And Nursing CareBriarcliff Manor, New York Survey Completed on 03-20-2025

Summary

The facility was found to be non-compliant with the 2011 NFPA 70 National Electrical Code Article 400.8, which prohibits the use of flexible cords and cables as a substitute for fixed wiring unless specifically permitted. During a Life Safety recertification survey, it was observed that refrigerators in the recreation office and the Director of Nursing office were plugged into power strips instead of directly into wall outlets. Additionally, in a resident room, a power strip was daisy-chained to a multiple adapter, which was then plugged into a wall outlet, with the resident's personal equipment connected to the power strip. These findings were noted on one of two resident floors and in the basement. The Director of Maintenance acknowledged the issue during an interview and stated that corrective action would be taken.

Plan Of Correction

Plan of Correction: Approved April 11, 2025 K920 I. Immediate Corrective Action: 1. Refrigerators Plugged into Power Strips: - On 3/19/25, the Director of Maintenance immediately disconnected the refrigerators in the Recreation Office and the Director of Nursing Office from the power strips. - The refrigerators were plugged directly into wall outlets to comply with NFPA 70 standards. 2. Daisy-Chained Power Strips in Resident Room: - On 3/19/25, the Director of Maintenance immediately addressed the issue in Resident Room B-27 by disconnecting the daisy-chained power strip and multiple adapters. - The equipment was properly reconfigured with a single, correctly rated power strip, plugged directly into a wall outlet. - The resident's personal equipment was safely reconnected. II. Identification of Others: - All residents have the potential to be affected. - A facility-wide audit of all power strips and adapters in resident rooms, offices, and common areas was conducted on 3/19/25. The audit identified no additional instances of daisy-chaining or refrigerators plugged into power strips. - NO further issues were noted. III. Systemic Changes: 1. The Director of Maintenance updated the facility's Electrical Safety Policy to ensure all electrical devices, including refrigerators and personal equipment, are directly connected to wall outlets unless explicitly approved by an electrical engineer or licensed contractor. - The policy now includes strict guidelines on the proper use of power strips and prohibits daisy-chaining of power strips or adapters. 2. All staff, including maintenance and housekeeping, received an in-service on NFPA 70 electrical safety standards, focusing on proper usage of power strips, avoiding daisy-chaining, and ensuring that appliances are plugged directly into outlets where applicable. 3. The facility will ensure that all residents and or family members will be informed of the proper use of power strips in the facility by the following methods: - Maintenance Director will hang up signage around the facility and discuss by monthly resident council the appropriate methods to use power strips. - Additionally, the Maintenance Director will draft a policy/notice that will be placed at the front desk for all families to see as well as mailing/emailing to all family members this notice on the appropriate usage of power strips. IV. Quality Assurance: 1. The Director of Maintenance created an audit tool to track compliance with NFPA 70 regarding power strips, adapters, and appliance connections. - The facility will conduct monthly audits for six months of all areas to ensure that no power strips are used inappropriately or daisy chained. - The results of these audits will be reported to QAPI quarterly. V. Person Responsible: - Director of Maintenance

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
C
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Extension Cords and Power Strips for Window AC Units
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that multiple window AC units throughout the facility were retrofitted by removing factory GFCI power cords and attaching extension cords, eliminating original electrical protections. One AC unit in the Dietary Director's office was also plugged into a power strip, contrary to regulations. Facility leadership confirmed these modifications, which violated electrical safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙