K0511 K511: Have properly installed electrical wiring and gas equipment.
E

Non-Compliance with NFPA 70 Electrical Code

Complete Care At Harston Hall LlcFlourtown, Pennsylvania Survey Completed on 05-01-2025

Summary

The facility failed to comply with NFPA 70, National Electric Code, for electrical wiring and equipment, affecting two of three levels in the facility. On the second floor, a non-GFCI outlet was observed within 6 feet of a sink in the Mechanical Room, which is a violation of NFPA 70 210.8(B)5 that requires a GFCI outlet in such locations. Additionally, storage was found within three feet of electrical panels in several locations, including the third floor Mechanical Room and next to Clean Linen areas on both the second and third floors, violating NFPA70 110.26(A)(1) which mandates a 3 ft. clearance in front of electrical equipment. Furthermore, an unsecured junction box was observed above the smoke barrier next to a resident room on the third floor. These deficiencies were confirmed during an exit interview with the Maintenance Director.

Plan Of Correction

1: Outlet was changed to a GFCI over the sink. 2: Storage was removed from the room. National Electric Code, for electrical wiring and equipment, affecting two of three levels in the facility. a. 9:39 a.m., on the third floor, Mechanical Room; box was removed and in-serviced staff on the importance of keeping that area free from items. b. 9:45 a.m., on the third floor, next to Clean Linen; wheelchair was in the cubby hole, was removed and staff in-serviced on the importance of keeping that area free from items. c. 9:50 a.m., on the second floor, next to Clean Linen; wheelchair was in the cubby hole/chair removed and staff in-serviced on the importance of keeping that area free from items. Unsecured junction box above the smoke barrier next to resident room 312 was fixed and secured.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0511 citations
Improper Fastening of Circuit Breaker Panel Cover with Sheet Metal Screws
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors found that a circuit breaker panel cover in one smoke compartment was improperly fastened with sheet metal screws instead of appropriate blunt-end fasteners, in violation of NFPA 70 requirements. The maintenance director acknowledged the use of sheet metal screws on the panel cover, and the report notes that this noncompliance could result in electric or fire hazards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improperly Labeled and Maintained Electrical Panels
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors identified that the facility’s electrical system was not maintained according to NFPA 101 and NFPA 70. In the kitchen electrical panel, breakers labeled for the dishwasher were in the off position while the dishwasher continued to run with power. In generator sub panel B, a breaker was labeled for a sprinkler pump even though no sprinkler pump existed, and there was an open breaker position without a blank cover. These issues were confirmed by the Maintenance Director and had the potential to affect all residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Non-GFCI Electrical Outlet Near Sink in Medication Room
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed that an electrical outlet in Nursing Station 1's med room was installed 18 inches from a sink and was not equipped with a required ground-fault circuit interrupter (GFCI), as mandated by NFPA 70, National Electrical Code. The DES confirmed during the survey that this outlet lacked GFCI protection, resulting in a cited deficiency related to utilities and electrical safety in one of the facility’s smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Exposed Electrical Wiring Due to Missing Junction Box Cover
E
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical junction box above the Zone 8 suspended ceiling, near the smoke barrier doors by the Unit Scheduler's Office, was found without a cover plate, leaving electrical wiring exposed. The Director of Maintenance confirmed the issue during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Noncompliance with Gas and Electrical Safety Standards
F
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

Surveyors observed multiple deficiencies including broken light bulb bases left in ceiling sockets, combustible materials stored too close to electrical panels, and exposed wiring behind a boiler. These issues were confirmed by facility leadership during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Broken Electrical Outlet Faceplate at Nurse Station
D
K0511 K511: Have properly installed electrical wiring and gas equipment.
Short Summary

An electrical outlet at Nurse Station #2 was found with a broken faceplate, exposing metal terminals. The CMO confirmed the damage had not been previously noticed. Facility policy assigns the Maintenance Director responsibility for maintaining safe equipment, but the exposed outlet was not addressed as required by NFPA 70.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer