K0920 K920: Ensure proper usage of power strips and extension cords.
E

Improper Suspension of Power Strips in Facility Offices

Tampico Healthcare CenterWalnut Creek, California Survey Completed on 04-02-2025

Summary

Surveyors observed that the facility failed to maintain electrical equipment in accordance with NFPA 101 and NFPA 70 standards. Specifically, power strips were found suspended under adjustable desks in both the Social Services Office and the Physician's Office near the North Nurse station. In both instances, the power strips were powering computer components and were suspended above the floor, with one approximately 12 inches and the other about three inches above the floor. Staff confirmed that the suspension of the power strips was likely due to the use of adjustable desks in these areas. The deficiency affected 43 of 123 residents and two of four smoke compartments. The report notes that the improper suspension of power strips could result in an electrical fire, as tension on the cords may be transmitted to joints or terminals, which is not compliant with the cited NFPA codes. No specific resident medical history or condition at the time of the deficiency is mentioned in the report.

Plan Of Correction

Preparation and execution of this plan of correction does not constitute admission or agreement by this provider of the truth of the facts alleged or conclusions set forth in the Statement of Deficiencies. The plan of correction is prepared and executed solely because it is required by the provisions of federal and state law. I. Corrective Action The facility will ensure to maintain electrical equipment of power strips. On 04/02/2025, Maintenance Director adjusted the power strips on both the desks of Social Services and in Physician's Office. The adjustment consisted of the power strips not to be suspended related to usage of the adjustable desks. II. Identify Other Residents at Risk On 04/03/2025, the Maintenance Director rounded each office to check suspension of all other power strip cords. No other power strip was identified with the same deficiency. No residents were affected. III. Systematic Changes On 04/02/2025, the Administrator had 1:1 in-service with Maintenance Director on proper placement of power strips (Attachment 4). On 04/03/2025, the Administrator conducted an in-service with office staff on proper placement of power strips (Attachment 5). IV. Monitoring Process Maintenance Director will perform a weekly audit of all power strips in the facility to ensure proper placement and not suspended for 3 months until compliance is met, the monthly audits thereafter. Findings will be reported to Administrator in the daily operations meeting. Administrator will report any findings and trends monthly to the QA Committee for 3 months or until compliance is met. V. Completion Date 04/14/2025

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
C
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Extension Cords and Power Strips for Window AC Units
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that multiple window AC units throughout the facility were retrofitted by removing factory GFCI power cords and attaching extension cords, eliminating original electrical protections. One AC unit in the Dietary Director's office was also plugged into a power strip, contrary to regulations. Facility leadership confirmed these modifications, which violated electrical safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙