K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
D

Missed Annual Inspection of Portable Fire Extinguisher

Adventist Health DelanoDelano, California Survey Completed on 04-15-2025

Summary

The facility failed to maintain portable fire extinguishers in accordance with NFPA 10 standards, as evidenced by a missed annual inspection. During a facility tour, surveyors observed that the exterior portable fire extinguisher located adjacent to the generator had an inspection tag dated over a year prior. The Maintenance Director confirmed that the annual inspection had not yet been completed at the time of the survey. This deficiency affected one of two smoke compartments and impacted 23 of 45 residents.

Plan Of Correction

K 355 Immediate Correction: The fire extinguisher was replaced with one that had completed the annual inspection timely. This finding had the potential to affect all residents. No harm was identified. Sustainment: The Facilities Staff was educated by the Facilities Manager on the importance of ensuring all fire extinguishers have their required inspection and maintenance. See attached education signature sheet. Monitoring: The specified fire extinguisher location will be included in ongoing EOC rounds to ensure it doesn't get missed again in the future due to its remote location. Data will be collected and reported out to the EOC Committee and the SCU Quality Assurance committee as part of the facility QAPI program. Person Responsible: Facilities Manager

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0355 citations
Blocked Portable Fire Extinguisher Identified
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher next to a resident room was found to be blocked during an observation, and this was confirmed by facility leadership during the exit interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Document Monthly Fire Extinguisher Inspections
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation confirming that basement portable fire extinguishers were inspected monthly as required, with no records available for several months. This was confirmed by the Administrator during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not provide documentation for annual fire extinguisher maintenance and technician certification, and a fire extinguisher in the main kitchen was found blocked. These deficiencies were confirmed by facility leadership during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure to Maintain and Inspect Portable Fire Extinguishers per NFPA 10
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

The facility did not ensure portable fire extinguishers were properly inspected and maintained according to NFPA 10, with one extinguisher lacking inspection records and another found overpressurized. These issues were confirmed by the Maintenance Director and could impact 15 occupants.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Installation and Accessibility of Portable Fire Extinguishers
F
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

Surveyors found that 12 out of 18 portable fire extinguishers were installed with the top of the handle positioned above the sixty-inch maximum height allowed by NFPA 101 and NFPA 10, with some as high as sixty-three inches. In one case, a trash can obstructed access to a fire extinguisher cabinet. The Maintenance Director acknowledged these findings during the inspection.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Missing Fire Extinguisher Maintenance Documentation
E
K0355 K355: Properly select, install, inspect, or maintain portable fire extinguishes.
Short Summary

A portable fire extinguisher in the kitchen service hallway was found without the required monthly maintenance and inspection tag, indicating a failure to document compliance with NFPA 10 standards. This was confirmed by the Maintenance Director and Administrator during surveyor interviews.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙