K0920 K920: Ensure proper usage of power strips and extension cords.
D

Incomplete Fire Drill Records and Improper Use of Electrical Equipment

Willow Pass Healthcare CenterConcord, California Survey Completed on 03-20-2025

Summary

The facility failed to maintain complete fire drill records, as evidenced by the absence of documentation for fire drills conducted during the AM shift in the fourth quarter of 2024. During a record review and interview, the Administrator was unable to provide the required fire drill records and could not locate them in the designated binders. The facility was given an opportunity to submit the missing records by email, but no records were received by the specified deadline. This deficiency affected all 77 residents across three smoke compartments. Additionally, the facility did not maintain electrical equipment in accordance with regulatory requirements. Observations revealed the use of extension cords and daisy-chained power strips in several areas, including the Main Entrance, Kaiser Room, and Dietary Supervisor's Office. Specifically, extension cords were used to power a wander guard detector and a portable air conditioning unit, while a power strip was found powering another power strip for computers and monitors. The Maintenance Director confirmed these setups were due to insufficient outlets and the need to power specific equipment.

Plan Of Correction

Systemic Changes As a new system, the safety committee monthly meeting will review the documentation to ensure the plan of correction is sustained and completed. Any discrepancy will be addressed to the maintenance supervisor and administrator immediately. Monitoring Process Maintenance supervisor will monitor for compliance monthly. This plan of correction is integrated into the monthly QA committee for its effectiveness and completeness. Completion Date This plan of correction will be completed on 04/18/2025. Corrective Action Maintenance director removed the yellow extension cord at the main entrance. Wander guard system is directly connected to the main power. Facility immediately removed the power strip from the kaiser room. The maintenance director will make sure that all electrical equipment is connected directly to the power outlet in the wall. Maintenance director and dietary manager removed the extension cord from the dietary manager's office and the portable air conditioner connected directly to the wall outlet. Identify other residents Maintenance director will do walk through the facility to make sure that this deficiency is not repeating in any other rooms. Any similar violations will be corrected immediately. Safety committee members will assist the maintenance director to identify any similar violations at the facility. Systemic Changes As a systemic change, the DSD and maintenance director will conduct an in-service to housekeeping and maintenance staff to re-educate them about the importance of not having any extension cords in the rooms & hallway. Housekeeping will assist and report to the maintenance director if they see any similar violations anywhere in the facility, and maintenance will correct it immediately. Monitoring Process Maintenance supervisor will monitor for compliance monthly. Administrator will oversee the process with the help of the safety committee members. QA Process This plan of correction is integrated into the monthly QA committee for its effectiveness and completeness. Completion Date This plan of correction will be completed on 04/18/2025.

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0920 citations
Improper Use of Power Strips and Extension Cords in Multiple Facility Areas
E
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found multiple instances of improper use of relocatable power taps (RPTs) and extension cords during a facility tour with the Maintenance Director. In the social services office, an RPT was plugged into another RPT connected to a wall outlet, with the cord running across a walkway and taped to the floor. In the multipurpose room, a television was plugged into an extension cord, and in the MDS office, an RPT was plugged into another RPT with an outlet adapter in use. These conditions did not comply with NFPA 101, NFPA 99, and NFPA 70 standards governing electrical equipment, power strips, and extension cords.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Power Strip as Permanent Power Source in Electrical Room
C
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that the facility failed to comply with NFPA 99, NFPA 70, and NFPA 1 requirements for electrical equipment when, during a tour with the Maintenance Director, a power strip in the electrical room was observed being used as a permanent power source instead of a dedicated receptacle. The report states that this improper use of a relocatable power tap could lead to electrical hazards for residents and staff, and notes that extension cords and power strips are not to be used as substitutes for fixed wiring under the cited codes.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Adapters and Power Strips for Refrigerators
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors observed that an adapter was used to power a refrigerator in the kitchen and a refrigerator in the dining room manager's office was plugged into a power strip. The Director of Facilities confirmed both uses, which did not comply with NFPA 99 and NFPA 70 requirements prohibiting adapters and power strips from being used as substitutes for permanent wiring.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Outlet Multiplier in Salon
D
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A three-to-one outlet multiplier was found in use in the first floor salon, with a hair dryer, hair straightener, and hair curler plugged into it, in violation of electrical equipment requirements. The maintenance director confirmed this setup during an interview.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Unapproved Power Strip Causes Electrical Fire at Bedside
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

A power strip not meeting required UL standards was found in use at a bedside, resulting in an electrical fire. The device had been brought in by a family member for charging a phone, and the facility could not verify its compliance with safety standards. This deficiency affected multiple residents and a smoke compartment.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Improper Use of Extension Cords and Power Strips for Window AC Units
F
K0920 K920: Ensure proper usage of power strips and extension cords.
Short Summary

Surveyors found that multiple window AC units throughout the facility were retrofitted by removing factory GFCI power cords and attaching extension cords, eliminating original electrical protections. One AC unit in the Dietary Director's office was also plugged into a power strip, contrary to regulations. Facility leadership confirmed these modifications, which violated electrical safety standards.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer