K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
F

Smoke Barrier Doors Failed to Close During Fire Alarm Testing

Ceres Postacute CareCeres, California Survey Completed on 05-19-2025

Summary

During a facility tour and interviews, surveyors observed that the smoke barrier doors adjacent to Rooms 15 and 13, as well as the doors near Rooms 8 and the Dining Room, failed to release from their magnetic door holders and close during fire alarm testing. The testing included activation of a smoke detector, pull station, and waterflow test, but the doors did not respond as required. The doors are intended to close automatically in response to fire alarm system activation to prevent the spread of smoke and fire between compartments. The Maintenance Assistant stated that the doors typically close when only the pull station is tested, but during this inspection, the doors did not function as expected. A sprinkler vendor present at the time believed the doors only close when the sprinkler system is activated. This discrepancy in understanding and the failure of the doors to operate correctly during multiple types of fire alarm activations were directly observed by surveyors. This deficiency affected all 43 residents in the three smoke compartments of the facility. The failure of the smoke barrier doors to close and latch as required by NFPA 101 and related standards was confirmed through direct observation and staff interviews during the survey.

Plan Of Correction

How corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: Fire Alarm System vendor was contacted immediately on 05/19/25. Repair to the automatic door releases were completed. A fire watch was instituted during the repair period. Facility was approved to be taken off from fire watch the following day by Life and Safety. How the facility will identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken: All residents have the potential to be affected by this deficient practice. No residents were found to be affected by this deficient practice. What measures will be put into place or what systemic changes in the facility will make to ensure that the deficient practice does not recur: Maintenance will be doing random tests/checks to ensure proper function. How the facility plans to monitor its performance to make sure that solutions are sustained: The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The Administrator shall report the outcome of the checks/inspections to the Quality Assurance and Assessment Committee (QA&A) during its monthly meeting. If determined that the facility has accomplished the objectives in the plan of correction as aforementioned and the results are successful, then the facility shall consider the matter resolved. The QA&A Committee shall continue to review until such time that the deficiency has been proven to be resolved for 3 consecutive months and/or as advised by the QA&A Committee. Date of Completion of Corrective Action: 05/20/25 How the facility plans to monitor its performance to make sure that solutions are sustained (repeated section): The facility must develop a plan for ensuring that correction is achieved and sustained. This plan must be implemented, and the corrective action evaluated for its effectiveness. The POC is integrated into the quality assurance system. The Administrator shall report the outcome of the checks/inspections to the Quality Assurance and Assessment Committee (QA&A) during its monthly meeting. If determined that the facility has accomplished the objectives in the plan of correction as aforementioned and the results are successful, then the facility shall consider the matter resolved. The QA&A Committee shall continue to review until such time that the deficiency has been proven to be resolved for 3 consecutive months and/or as advised by the QA&A Committee. Date of Completion of Corrective Action: 05/20/25

Penalty

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
See other K0374 citations
Failure to Maintain Smoke Barrier Doors to Resist Passage of Smoke
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors identified that smoke barrier doors in two areas of the facility were not maintained to resist the passage of smoke. In one hallway outside a nurse's station, the smoke barrier doors did not close smoke-tight because the door frame was unsecured within the wall. In another area outside the lobby, the smoke barrier doors failed to swing and close smoke-tight due to a broken door closer, and this problem remained uncorrected at a later revisit survey, as confirmed by the Administrator and Maintenance Director.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Close Smoke-Tight
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Smoke barrier doors near the Laundry Area did not fully close when released from hold-open devices, resulting in a failure to maintain smoke-tight conditions as required. Facility leadership confirmed the deficiency during the survey.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Self-Close and Latch
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a third-floor room failed to self-close and latch when tested, affecting two smoke compartments. Facility leadership confirmed the deficiency.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Door Hardware Failed to Latch Properly
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that the double smoke barrier door between two compartments did not latch as required, with the hardware failing to function per manufacturer specifications. This issue was confirmed by the Director of Facilities and affected two smoke compartments.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Failure of Fire/Smoke Barrier Doors to Close as Required
E
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors found that several fire/smoke barrier doors, including those near the DON office and in resident rooms, were unable to close properly during both routine checks and a fire alarm test. Staff confirmed they were unaware of the closure requirements for these doors, resulting in noncompliance with NFPA 101-2012 standards and potentially affecting multiple residents.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.
Smoke Barrier Doors Failed to Achieve Smoke-Tight Fit
F
K0374 K374: Install smoke barrier doors that can resist smoke for at least 20 minutes.
Short Summary

Surveyors observed that smoke barrier doors near a resident room and by a nurses station leading to the dining room did not fully close and latch to a smoke-tight fit as required by LSC. The Maintenance Director confirmed these findings.

No penalty information released
tooltip icon
The penalty, as released by CMS, applies to the entire inspection this citation is part of, covering all citations and f-tags issued, not just this specific f-tag. For the complete original report, please refer to the 'Details' section.

Know what gets cited — and walk into your next survey with full visibility

We process and analyze inspection reports and Plans of Correction using AI to surface insights and trends — so you can improve care quality and stay ahead of compliance risk before your next survey.

Get ready for your next survey

See what surveyors are citing in your state and spot your risk areas before they do.

Monthly Citation Reports

Have you been cited for this tag?

Save hours drafting a compliant Plan of Correction — AI built on real approved POCs.

Plan of Correction Writer

Trusted data from CMS and state health departments

Every citation, penalty and Plan of Correction is sourced from public CMS records (latest release June 24, 2026) and official state health department websites — never guesswork.

Trusted by long-term care providers and associations.

Allegria Senior Living logo
FHCA logo
WeCare Centers logo
Care Rehab logo
An unhandled error has occurred. Reload 🗙